4 Reattach the side panel. Ensure the water can flow through the
drain tube.
It is recommended to use a tundish to collect the water.
Option 1: Through the left side panel
T25
1
Option 2: Through the right side panel
1
T25
5

Piping installation

5.1

Preparing water piping

NOTICE
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN  4726. The diffusion of
oxygen into the piping can lead to excessive corrosion.
NOTICE
Water circuit requirements. Make sure to comply with the
water pressure and water temperature requirements
below. For additional water circuit requirements, see the
installer reference guide.
▪ Water pressure – Domestic hot water. The maximum water
pressure is 4 bar. Provide adequate safeguards in the water circuit
to ensure that the maximum pressure is NOT exceeded. The
minimum water pressure to operate is 1 bar.
ETVH16SU18+23EA6V
Daikin Altherma 3 H HT F
4P644729-1 – 2021.02
▪ Water pressure – Space heating/cooling circuit. The maximum
water pressure is 3 bar. Provide adequate safeguards in the water
circuit to ensure that the maximum pressure is NOT exceeded.
The minimum water pressure to operate is 1 bar.
▪ Water temperature. All installed piping and piping accessories
(valve,
connections,...)
MUST
temperatures:
INFORMATION
The following illustration is an example and might NOT
match your system layout.
75°C (*)
(*) Maximum temperature for piping and accessories
5.1.1

To check the water volume and flow rate

Minimum water volume
Check that the total water volume in the installation is minimum 20
litres, the internal water volume of the outdoor unit NOT included.
NOTICE
When circulation in each space heating/cooling loop is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.
Minimum flow rate
Check that the minimum flow rate in the installation is guaranteed in
all conditions. This minimum flow rate is required during defrost/
backup heater operation. For this purpose, use the overpressure
bypass valve delivered with the unit, and respect the minimum water
volume.
Minimum required flow rate
25 l/min
NOTICE
To guarantee proper operation it is recommended to have
a minimum flow of 28 l/min during DHW.
NOTICE
If glycol was added to the water circuit, and the
temperature of the water circuit is low, the flow rate will
NOT be displayed on the user interface. In this case, the
minimum flow rate can be checked by way of the pump
test (check that the user interface does NOT display error
7H).
5 Piping installation
withstand
the
following
89°C (*)
75°C (*)
M
Installation manual
9