Hearth and Home Technologies QUADRA-FIRE Village QV32B-A Installer's Manual page 23

Table of Contents

Advertisement

NOTE: There MUST be a 25%
reduction in total H when using
flex vent except when using
the simple up and out installa-
tion (see Figure 9).
Use SL D-Series components only.
Figure 16. Venting with Two 90° Elbows
VENTING WITH TWO (2) 90
V (MIN.)
90
o
Elbow on Top
1 FT (305mm)
2 FT (610mm)
3 FT (914mm)
4 FT (1.22m)
5 FT (1.52m)
H MAX. = 16 FT (4.8m)
VENTING WITH TWO (2) 90
V (MIN.)
o
90
Elbow on Top
1 FT (305mm)
2 FT (610mm)
3 FT (914mm)
4 FT (1.22m)
5 FT (1.52m)
H MAX. = 16 FT (4.8m)
V
1
Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
o
ELBOWS
NATURAL GAS
H (MAX.)
2 FT (610mm)
3 FT (914mm)
4 FT (1.22m)
6 FT (1.86m)
8 FT (2.48m)
16 FT (4.8m)
V + V
+ H MAX. = 40 FT (12.2m)
1
o
ELBOWS
PROPANE
H (MAX.)
NOT ALLOWED
2 FT (610mm)
4 FT (1.22m)
6 FT (1.86m)
8 FT (2.48m)
16 FT (4.8m)
V + V
+ H MAX. = 40 FT (12.2m)
1
H
V
23