Wieland ricos FLEX BC MODBUS User Manual page 42

Table of Contents

Advertisement

Parameters
Here you can change the current parameters of the ricos FLEX BC MODBUS.
Parameters
Link monitoring
Communication
timeout [ms]
Socket timeout
[ms]
IO cycle [µs]
Diagnosis
Security
All functions for the writing access to the Ethernet coupler can be secured by a password.
IP
Here you may assign to your Ethernet coupler IP address data. For valid IP address data please con-
tact your system administrator.
Firmware
Information about the firmware.
Wieland Electric GmbH | BA001269 | 09/2021 (Rev. A)
Data type
Range
BOOL
TRUE/FALSE
UINT_32
• 0 ... 30000
• 0 ... 30000
UNIT 32
• 0
UINT_32
• 1000
• 2000
• 4000
• 8000
• 10000
Link monitoring
o
As soon as both Ethernet cables are pulled with enabled Link monitoring, the com-
munication is finished by the ricos FLEX BC MODBUS, BASP (Befehls-Ausgabe-
Sperre, i.e. command output disable) is activated and this is indicated with flash-
ing SB LED. Link monitoring reacts only when both Ethernet cables are pulled.
Communication timeout
o
At Communication Timeout [ms] you can specify a timeout value for Ethernet com-
munication in ms.
o
If there is no Modbus communication for the specified time, BASP is set on the ri-
cos FLEX bus.
o
With the value 0, you can deactivate the time monitoring.
IO cycle
o
With IO cycle, you can specify the cycle for the ricos FLEX bus within which the I/O
image is to be refreshed.
o
With the value 0 you can set the maximum possible cycle time (no delay).
Socket timeout
o
At Socket Timeout [ms] you can specify a timeout value for the Modbus socket
connection in ms.
o
If there is no Modbus communication on a specific Modbus socket connection for
the specified time, the corresponding socket is closed.
o
With the value 0, you can deactivate the time monitoring.
Configuration State: Deviations between the setpoint and actual configuration are shown
here (OK: no deviation).
Diagnosis Entries: Here all pending diagnostic messages are shown.
Diagnosis Buffer: Here the content of the diagnostics buffer is listed.
Default
Description
value
FALSE
Link monitoring Ethernet
0
Timeout Ethernet communication
0
Timeout Modbus socket connection
1000
ricos FLEX bus cycle
Deployment
42