7.1 Electric wiring
Input power line (LINE):
L1,L2 power line
GND ground
Analog inputs:
AN1 (4-20 mA or 0-10 V)
AN2 (4-20 mA or 0-10 V)
0V
+24V
AN3 (4-20 mA)
AN4 (4-20 mA)
0V
+24V
10V
0V
AN1 o AN2 terminals can be set as
voltage input (V) or current input (I)
through J5 e J9 selector.
L1
Output power line (PUMP):
M1,M2 terminals
GND ground
Digital inputs:
Communication
auxiliary (RS485):
IN1
0V
IN2
0V
IN3
0V
IN4
0V
Pump signal:
S+ (red)
S- (white)
Digital outputs (relays):
S1+
S1-
Relays of digital outputs are free
contacts relays (no voltage) Max
voltage is 250 V AC and max
current is 5 A.
RELAY1: pump run signal
NO: normally opened
COM: common
NC: normally closed
RELAY2: alarm signal
NO: normally opened
COM: common
NC: normally closed
9