7 Configuration
For more information and advice about the impact of these settings,
see
"7.3 Energy saving and optimum operation" on
[2‑9]
T
target temperature during heating operation.
c
[2‑9]
0 (default)
1
3
6
For more information and advice about the impact of these settings,
see
"7.3 Energy saving and optimum operation" on
[2‑18]
Fan high static pressure setting.
In order to increase the static pressure the outdoor unit fan is
delivering, this setting should be activated. For details about this
setting, see technical specifications.
[2‑18]
0 (default)
Deactivated.
1
Activated.
[2‑20]
Manual additional refrigerant charge.
In order to add the additional refrigerant charge amount in a manual
way (without automatic refrigerant charging functionality), following
setting should be applied. Further instructions regarding the different
ways to charge additional refrigerant into your system can be found
in chapter
"6.7.2 About charging refrigerant" on
[2‑20]
0 (default)
Deactivated.
1
Activated.
To stop the manual additional refrigerant
charge operation (when the required additional
refrigerant amount is charged), push BS3. If
this function was not aborted by pushing BS3,
the unit will stop its operation after 30 minutes.
If 30 minutes was not sufficient to add the
needed refrigerant amount, the function can be
reactivated by changing the field setting again.
[2‑21]
Refrigerant recovery/vacuuming mode.
In order to achieve a free pathway to reclaim refrigerant out of the
system or to remove residual substances or to vacuum the system it
is necessary to apply a setting which will open required valves in the
refrigerant circuit so the reclaim of refrigerant or vacuuming process
can be done properly.
[2‑21]
0 (default)
Deactivated.
1
Activated.
To stop the refrigerant recovery/vacuuming
mode, push BS3. If BS3 is not pushed, the
system will remain in refrigerant recovery/
vacuuming mode.
[2‑22]
Automatic low noise setting and level during night time.
By changing this setting, you activate the automatic low noise
operation function of the unit and define the level of operation.
Depending on the chosen level, the noise level will be lowered. The
start and stop moments for this function are defined under setting
[2‑26] and [2‑27].
Installer and user reference guide
36
page 37.
T
target (°C)
c
Auto
41
43
46
page 37.
Description
page 24.
Description
Description
[2‑22]
0 (default)
Deactivated
1
Level 1
2
Level 2
3
Level 3
[2‑25]
Low noise operation level via the external control adaptor.
If the system needs to be running under low noise operation
conditions when an external signal is sent to the unit, this setting
defines the level of low noise that will be applied.
This setting will only be effective when the optional external control
adaptor (DTA104A61/62) is installed and the setting [2‑12] was
activated.
[2‑25]
1
Level 1
2 (default)
Level 2
3
Level 3
[2‑26]
Low noise operation start time.
This setting is used in conjunction with setting [2‑22].
[2‑26]
Start time automatic low noise operation
1
2 (default)
3
[2‑27]
Low noise operation stop time.
This setting is used in conjunction with setting [2‑22].
[2‑27]
Stop time automatic low noise operation
1
2
3 (default)
[2‑30]
Power consumption limitation level (step  1) via the external control
adaptor (DTA104A61/62).
If the system needs to be running under power consumption
limitation conditions when an external signal is sent to the unit, this
setting defines the level power consumption limitation that will be
applied for step 1. The level is according to the table.
[2‑30]
Power consumption limitation
1
2
3 (default)
4
5
6
7
8
[2‑31]
Power consumption limitation level (step  2) via the external control
adaptor (DTA104A61/62).
VRV IV+ heat pump for high ambient temperatures
Description
Level 3<Level 2<Level 1
Description
Level 3<Level 2<Level 1
(approximately)
20h00
22h00
24h00
(approximately)
6h00
7h00
8h00
(approximately)
60%
65%
70%
75%
80%
85%
90%
95%
RXYTQ8~16U7YF
4P561157-1 – 2018.09