Daikin Altherma 3 H MT F Installer's Reference Manual page 107

Hide thumbs Also See for Altherma 3 H MT F:
Table of Contents

Advertisement

EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
b
L
a
N
b
L
1N~,
50 Hz,
N
230 V AC
a Power supply cable (field supply)
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 2 pole, 32 A fuse, C curve.
Q1DI Earth leakage circuit breaker (30 mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block (make sure the numbers match with
the numbers on the indoor unit) and the earth screw.
▪ Fix the cable with a cable tie.
Wires: (3+GND)×1.5 mm²
L N PE
F1B
Q1DI
BRN
2
1
BLU
4
3
YLW/GRN
9
Electrical installation
|
a
Installer reference guide
107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents