Omron K8DT-TH Manual page 11

Temperature monitoring relay
Table of Contents

Advertisement

Screw Mounting
1. Pull out the two hooks on the back of the Relay to the outside until
you hear them click in place.
2. Insert M3 screws into the hook holes and secure the Relay.
(1)
(2)
(1)
Note: 1. Pull out the hooks to mount
(2)
Adjusting the Setting Knobs
• Use a flat-blade screwdriver to adjust the setting knobs.
Setting knob
Connecting Wires to the Push-In Plus Terminal Block
Part Names of the Terminal Block
<Upper side>
Terminal
(Insertion) hole
Release hole
Connecting Wires with Ferrules and Solid Wires
Insert the solid wire or ferrule straight into the terminal block until the
end strikes the terminal block.
<Upper side>
Terminal
(Insertion) hole
Ferrule
Release hole
If a wire is difficult to connect because it is too thin, use a flat-blade
screwdriver in the same way as when connecting stranded wire.
Mounting Hole Dimensions
Two M3 screw holes or
two 3-dia. holes
108
the Relay with screws.
2. Recommended tightening
torque: 0.5 to 0.6 N·m.
<Lower side>
Release hole
Terminal
(Insertion) hole
<Lower side>
Release hole
Ferrule
Terminal
(Insertion) hole
Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal block.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole. The angle should be between 10° and 15°.
If the flat-blade screwdriver is inserted correctly, you will feel the
spring in the release hole respond.
2. With flat-blade screwdriver still inserted into the release hole, insert
the wire into the terminal hole until it strikes the terminal block.
3. Remove the flat-blade screwdriver from the release hole.
<Upper side>
(2)
Wire
(3)
(1)
Flat-blade screwdriver
10 to 15°
Flat-blade
screwdriver
Checking Connections
• After the insertion, pull gently on the wire to make sure that it will
not come off and the wire is securely fastened to the terminal block.
• If you use a ferrule with a conductor length of 10 mm, part of the
conductor may be visible after the ferrule is inserted into the
terminal block, but the product insulation distance will still be
satisfied.
Removing Wires from the Push-In Plus Terminal Block
Use the following procedure to remove wires from the terminal block.
The same method is used to remove stranded wires, solid wires, and
ferrules.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
remove the wire from the terminal insertion hole.
3. Remove the flat-blade screwdriver from the release hole.
<Upper side>
(2)
Wire
(3)
(1)
Flat-blade screwdriver
10 to 15°
Flat-blade
screwdriver
K8DT-TH
<Lower side>
Flat-blade screwdriver
(3)
(1)
Wire
(2)
Flat-blade
screwdriver
10 to 15°
<Lower side>
Flat-blade screwdriver
(3)
(1)
Wire
(2)
Flat-blade
screwdriver
10 to 15°
11