9.3 Remote Control MODBUS RTU protocol supported parameters
Depending on installed hardware, modbus interface connection support data over TCP/IP, RS485, or RS232.
- TCP/IP is user configurable
- RS485, and RS232, ordered as option with code 02-04-227, support fixed baud rate 9600 8N1
1. LIGHTS CONTROL*:
Address range:
Address
00001
00002
00199
2. LIGHTS STATUS:
Address range:
Address
40001
40002
4
0199

3. SYSTEM STATUS :

Address range:
Address
40200
40201
40202
40203
40204
(1) Common alarm flag summarizes all light, main and spare power
supply, and modules communication alarms
(2) Lights alarm indicates one or more lights contain alarms
(3) Power supply alarm indicates main or spare power supply contain
alarm
(4) Module alarm indicates one or more modules contain alarm, user
should acknowledge alarm from main unit ITNSL-01TP
4. GROUPS CONTROL*:
and turn on only the lights associated with configured group.
This command relftects, if turned on lights belongs to predefined
group.
Address range:
Address
40205
* IMPORTANT! User should take care when using Lights
control and groups control in the same system, ITNSL-01P
software will process last command recieved.
5. ALARM ACCEPTANCE:
Address range:
Address
40206
Turn on/off of each individual light
Configured lights in ITNSL-01TP:
Light no. 1
Light no. 2
Light no. 199
Read status of each individual light
Configured lights in ITNSL-01TP:
Light no. 1
Light no. 2
Light no. 199
Description:
(1)
Common alarm
(2)
Lights alarm
(3)
Power supply alarm
Module communication alarm
Modbus RTU write
Turn off all lights at once,
Configured groups in ITNSL-01TP:
Turn off all lights /or turn on only one
configured group
Mute external alarm output,
and acknowledge of all
current alarms.
Description:
Mute / acknowledge of current
system and/or lights alarms
Supported modbus functions:
Code
05
15
Light control value:
Value
0
1
Supported modbus functions:
Code
03
Light status value:
Value
0x0000
0x0001
0x0002
0x0003
0x0004
Supported modbus functions:
Code
03
}
Alarm acknowledge value:
Value
0x0001
(4)
0x0002
0x0003
Value
0x0000
0x0001
Supported modbus functions:
Code
03
06
Group control value:
Value
0x0000
0x0001
0x0002
0x0003
0x0028
0xFFFF
Supported modbus functions:
Code
06
Alarm acknowledge value:
Value
0x0001
0x0002
48
NL95
Name:
write single coil
write multiple coils
Description:
Turn off light
Turn on light
Name:
read holding registers
Description:
Light not present or not connected
Light off
Light main on
Light spare on
Light alarm
Name:
read holding registers
Description:
Status OK
Alarm exists
Alarm acknowledged, and exists
Description:
Disabled
Enabled
Name:
read holding registers
write single register
Description:
Turn off lights /or All lights is OFF
Turn on Group no. 1
Turn on Group no. 2
Turn on Group no. 3
Turn on Group no. 40
(Read only) turned on light/s does
not belong to any group
Name:
write single register
Description:
Mute
Mute and acknowledge alarms