Trane TCONT900AC43UA Installer's Manual page 12

Hide thumbs Also See for TCONT900AC43UA:
Table of Contents

Advertisement

TCONT900AC43UA
Selection
Dehumidification
Airflow
Trane Proprietary
Humidity Control
Furnace Filter 1
Change Reminder
Pub. No. 18-HD32D1-2
69-2079—05
Table 4. Installer Setup Menu
Installer Setup
Factory
Number (ISU)
Setting
0387
100
0388
1
0500
E, 0
Choices
Option
Description
80 - 100
80 - 80% Airflow
85 - 85% Airflow
90 - 90% Airflow
95 - 95% Airflow
100 - 100% Airflow
0, 1
0 - Disabled
1 - Enabled
E, 0 - 14
E - Auto-Discover
0 - Disabled (reminder off)
1 - 10 run time days
2 - 30 run time days
3 - 60 run time days
4 - 90 run time days
5 - 120 run time days
6 - 180 run time days
7 - 270 run time days
8 - 365 run time days
9 - 30 continuous days
10 - 60 continuous days
11 - 90 continuous days
12 - 120 continuous days
13 - 180 continuous days
14 - 365 continuous days
12
Comments
Only shown for variable
speed indoor units. See
Advanced Features section
for more information
Not shown if ISU0380 is set
to 0.
See Advanced Features
section for more information
When set to Auto-Discover
(and the discovered value is
not 0=disabled), the
Comfort Control will display
the filter timer value it
receives from the
TM
ComfortLink
II
communicating filtering
device on the More screen.
To reset the filter timer of
TM
the ComfortLink
II
communicating filtering
device, simply press the
More key to access the filter
timer value and then press
the Reset key. If no
TM
ComfortLink
II
communicating filtering
device has been
discovered, the auto-
discovered value will default
to 0.
When not set to Auto-
Discover (and not set to
0=disabled), the Comfort
Control will display its
internal filter timer on the
More screen.
To reset the Comfort
Control's internal timer,
simply press the More key
to access the filter timer
value and then press the
Reset key.

Hide quick links:

Advertisement

Table of Contents
loading