Mitsubishi Electric MXZ-2HA40VF-E1 Service Manual page 64

Outdoor unit
Hide thumbs Also See for MXZ-2HA40VF-E1:
Table of Contents

Advertisement

2. Outdoor control P.C. board
MXZ-3HA50VF
CN741
Signal translation
(To Communication
adaptor board)
V
(Rotate signal)
FG
(Voltage between
right pins of PC931,
pin 3 and pin 4)
(Correspond to
(CNF1 (+)- (−))
V
(Rotate instruction)
SP
(Voltage between pins
of C930): 0 V DC
(when stopped),
1.8 - 6.5 V DC
(when operated)
(Same as
(CNF1 (+)- (−))
CNF1
To fan motor
Bus-bar voltage
290 - 370 V DC
15 V DC
Rotate instruction
(Constant voltage)
Rotate signal
(Pulse wave)
CNDC
Bus-bar
voltage
290 - 370
V DC
CN63H
High
pressure
switch
CN702
(+)
Signal transmission
15 V
(To power board)
(-)
5 V DC pulse wave
(-)
15 V
(-)
CN701
Signal transmission
(To power board)
5 V DC pulse wave
OBH828B
Serial signal 12 ~ 24 V
220 - 230 - 240 V AC
Room B
Room A
Room C
Input
CN601
(-)
(+)
CN611
CN793
CN791
LED3
LED2
LEV Room C
LEV Room A
LED1
CN792
CN797
LEV Room B
LEV Room R
LEV: 12 V DC
pulse wave
Discharge temperature thermistor (RT62)
800
700
600
500
400
300
200
100
0
0 10 20 30 40 50 60 70 80 90 100 110 120
64
Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature
thermistor (RT68)
100
90
80
70
60
50
40
30
20
10
0
-20
-10
0
10
20
30
Temperature
Thermistor R25 = 10 kΩ ± 2%
B constant = 3950 ± 2%
1
Rt = 10exp{3950(
273+t
F711 FUSE
T3.15AL250V
CNAC
to outdoor power P.C. board
220 - 230 - 240 V AC
Input
CN714 Defrost heater
220 - 230 - 240 V AC
Output
CN713 Valve coil
220 - 230 - 240 V AC
Output
CNTH2
Ambient temperature
thermistor
(RT65)
CNTH1
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
Defrost thermistor (RT61)
SW1
SW871
SW2
Temperature( )
Thermistor R100 = 13.36 kΩ ± 2%
B constant = 4014 ± 2%
1
1
Rt = 13.36exp{4014(
)}
273+t
373
40 (ºC)
1
)}
298

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents