Mitsubishi Electric MXZ-2HA40VF-E1 Service Manual page 43

Outdoor unit
Hide thumbs Also See for MXZ-2HA40VF-E1:
Table of Contents

Advertisement

3. Table of outdoor unit failure mode recall function
MXZ-2HA
Upper or
left lamp of
OPERATION
Abnormal point
INDICATOR
(Failure mode/protection)
lamp (Indoor
unit)
OFF
None (Normal)
2-time blink
Outdoor power system
3-time blink
Discharge temperature
thermistor
Defrost thermistor
Ambient temperature
thermistor
Fin temperature thermistor
P.C. board temperature
thermistor
Outdoor heat exchanger
temperature thermistor
4-time blink
Overcurrent
Compressor
5-time blink
Discharge temperature
6-time blink
High pressure
7-time blink
Fin temperature
P.C. board temperature
8-time blink
Outdoor fan motor
9-time blink
Nonvolatile memory data
Power module
10-time blink
Discharge temperature
11-time blink
Current sensor
Bus-bar voltage
14-time blink
Stop valve
17 time blink
Outdoor refrigerant system
abnormality
OBH828B
LED indication
(Outdoor P.C. board)
LED 1
LED 2
Not lit
Not lit
Lit
Lit
Overcurrent protection cut-out operates
3 consecutive times within 1 minute after
the compressor gets started.
Compressor protection cut-out
operates 24 consecutive times within
10 seconds after the compressor gets
started.
Lit
Once
Thermistor shorts or opens during
compressor running.
Lit
Once
Lit
Twice
Lit
3 times
Lit
4 times
Lit
9 times
Once
Not lit
The overcurrent flows into intelligent
power module.
Twice
Not lit
The overcurrent flows into intelligent
power module within 10 seconds after
the compressor gets started.
( The compressor gets restarted in
15 seconds.)
9 times
Not lit
Waveform of compressor current is dis-
torted.
Lit
Lit
Discharge temperature exceeds 116ºC
during operation.
Lit
Lit
The outdoor heat exchanger temperature
exceeds 70ºC during cooling or the indoor
gas pipe temperature exceeds
70ºC during heating.
3 times
Not lit
The fin temperature exceeds 90ºC
during operation.
4 times
Not lit
The P.C. board temperature exceeds
80ºC during operation.
Lit
Lit
Failure occurs 3 consecutive times
within 30 seconds after the fan gets
started.
Lit
5 times
Nonvolatile memory data cannot be read
properly.
7 times
Not lit
The output of the power module that
drove the compressor was shorted or
the winding of the compressor was
shorted.
Lit
Lit
The discharge temperature is kept
under 50ºC (COOL mode)/40ºC (HEAT
mode) for more than 40 minutes.
8 times
Not lit
The sensor circuit of current of
compressor shorts or opens during
compressor operate.
6 times
Not lit
The bus-bar voltage exceeds 430 V or
falls to 50 V or below during compres-
sor operating.
Lit
12 times The current of compressor is power
module is out of order.
Lit
17 times A closed valve and air trapped in the
refrigerant circuit are detected based on
the temperature sensed by the indoor and
outdoor thermistors and the current of the
compressor.
43
NOTE: Blinking patterns of this mode differ from the ones of
Troubleshooting check table (12-4).
Condition
• Check the compressor connecting
wire.
• Refer to 12-6.
inverter/compressor".
• Check the stop valve.
• Refer to 12-6.
door thermistors".
• Replace the inverter P.C. board.
• Refer to 12-6.
door thermistors".
• Check the compressor connecting
wire.
• Refer to 12-6.
inverter/compressor".
• Check the stop valve.
• Check the compressor connecting
wire.
• Refer to 12-6.
inverter/compressor".
• Check the refrigerant circuit and
the refrigerant amount.
• Refer to 12-6.
• Check the refrigerant circuit and
the refrigerant amount.
• Check the stop valve.
• Check the around outdoor unit.
• Check the outdoor unit air pas-
sage.
• Refer to 12-6.
door fan motor".
• Refer to 12-6.
door fan motor".
• Replace the inverter P.C. board.
• Refer to 12-6.
inverter/compressor".
• Check the refrigerant circuit and
the refrigerant amount.
• Refer to 12-6.
• Replace the inverter P.C. board.
• Check the power supply.
• Replace the inverter P.C. board.
• Check the stop valve.
• Check the refrigerant circuit and
the refrigerant amount.
• Check for a gas leak in a connecting
piping etc.
• Check the stop valve.
• Refer to 12-6.
door refrigerant circuit".
Indoor/
outdoor
unit failure
Remedy
mode
recall
function
"How to check
"Check of out-
"Check of out-
"How to check
"How to check
"Check of LEV".
"Check of out-
"Check of out-
"How to check
"Check of LEV".
"Check of out-