59SP6A: Installation, Start-up, Operating, Service and Maintenance Instructions
Maximum Allowable Exposed Vent Lengths in Unconditioned Space Insulation Table - Ft. / M (Continued)
Unit Size
Winter
Pipe Dia.
1 ½
Design
in.
Temp
20
15
°F
0
15
-20
15
-40
10
Unit Size
Winter
Pipe Dia.
2
Design
in.
Temp
20
20
°F
0
20
-20
15
-40
10
Unit Size
Uninsulated
Winter
Pipe Dia.
2 ½
3
Design
in.
Temp
20
10
50
°F
0
10
20
-20
10
10
-40
10
5
Maximum Allowable Exposed Vent Length in Unconditioned Space (Metric)
Unit Size
Uninsulated
Winter
Pipe Dia.
Design
38
51
mm
Temp
-7
6.1
6.1
°C
-18
3.0
1.5
-29
1.5
-40
Unit Size
Winter
Pipe Dia.
38
Design
mm
Temp
-7
4.6
°C
-18
4.6
-29
4.6
-40
3.0
Unit Size
Winter
Pipe Dia.
51
Design
mm
Temp
-7
6.1
°C
-18
6.1
-29
4.6
-40
3.0
Unit Size
Uninsulated
Winter
Pipe Dia.
Design
64
76
mm
Temp
-7
3.0
15.2
°C
-18
3.0
6.1
-29
3.0
3.0
-40
3.0
1.5
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length calculated from
† Insulation thickness based on R value of 3.5 per in.