59SP6A: Installation, Start-up, Operating, Service and Maintenance Instructions
EXAMPLE FOR
UPFLOW INSTALLATIONS.
MAY BE APPLIED TO
OTHER CONFIGURATIONS.
Fig. 46 – Sample Inlet Air Pipe Connection for Polypropylene
Venting Systems
12" (256mm) minimum
60"(1524 mm) or
1 additional elbow maximum
CASING SIDE OR TOP ATTACHMENT
COMBUSTION AIR PIPE
(NON-DIRECT VENT FOR ALL MODELS EXCEPT MODULATING UNLESS
INSTALLED IN ATTIC OR CRAWL SPACE)
Fig. 47 – Combustion Air Pipe Attachment
Fig. 48 – Pipe Vent and Combustion
!
RECOMMENDED SUPPORT FOR VENT TERMINATIONS
It is recommended that sidewall vent terminations in excess of 24
inches (.6 M) or rooftop terminations in excess of 36 inches (1 M) in
vertical length be supported by EITHER the Direct Vent Termination
Kit shown in
Table 12
or by field-supplied brackets or supports
fastened to the structure.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined below for each appliance
being placed into operation could result in carbon monoxide poisoning
or death.
For all venting configurations for this appliance and other gas
appliances placed into operation for the structure, provisions for
adequate combustion, ventilation, and dilution air must be provided in
accordance with:
USA Installations: Section 9.3 current edition of NFPA 54/ANSI
Z223.1 Air for Combustion and Ventilation and applicable provisions
of the local building codes.
Termination Requirements
Saskatchewan
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
to
A
NOTICE
for the Provinces of Alberta and
The Provinces of Alberta and Saskatchewan require a minimum
unobstructed distance of 4 ft. (1.2 M) from the foundation to the property
line of the adjacent lot for vent termination of any appliance with an
input over 35,000 Btuh. If there is less than 4 ft. (1.2 M) of unobstructed
distance to the property line of the adjacent lot, no type of vent
termination is permitted for appliances with inputs greater than 35,000
Btuh.
There are no additional restrictions on unobstructed distances greater
than 8 ft. (2.4 M). All single, two-pipe and concentric vents may be used,
providing all other Code and manufacturer's requirements in these
instructions are adhered to. Refer to the appropriate Vent Termination
section above for locating the vent termination
A12220
If the unobstructed distance from the foundation to the property line of
the adjacent lot is no less than 4 ft. (1.2 M) and no greater than 8 ft. (2.4
M), it will be necessary to re-direct the flue gas plume. In this situation, a
concentric vent kit cannot be used. A 2-pipe termination (or single pipe
termination when permitted) that re-directs the flue gas away by use of
an elbow or tee, certified to ULC S636 from the adjacent property line
must be used. See
Fig.
A13406
A96128
OPTIONAL
BRACKET
COUPLING
(ELBOW PARALLEL TO WALL)
Fig. 49 – Alberta and Saskatchewan Vent Termination
The concentric vent kit currently cannot be modified to attach an elbow
to the vent portion of the rain cap. A tee attached to the rain cap could
potentially direct the flue gas plume toward the intake air stream and
contaminate the incoming combustion air for the furnace.
Refer to
Fig. 49
for terminations approved for use in Alberta and
Saskatchewan.
42
49.
OPTIONAL TERMINATION
BRACKET FOR 2-PIPE
TERMINATIONS
12 IN. (305 MM) MIN.
SEPARATION BETWEEN
BOTTOM OF COMBUSTION
AIR AND BOTTOM OF VENT.
12-IN. (305 MM)
ABOVE ANTICIPATED
SNOW LEVEL
12 IN. (305 MM) MIN. SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR AND
BOTTOM OF VENT.
MAINTAIN 12 IN. (305 MM)
CLEARANCE ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE,
WHICHEVER IS GREATER.
COMBUSTION-AIR
OVERHANG
EXHAUST
CLEARANCE TO OVERHANG PER CODE
12 IN. (305 MM) MIN. GROUND
LEVEL OR ANTICIPATED SNOW LEVEL
A13078A