Carrier 59SP6B Installation, Start-Up, Operating, Service And Maintenance Instructions
Carrier 59SP6B Installation, Start-Up, Operating, Service And Maintenance Instructions

Carrier 59SP6B Installation, Start-Up, Operating, Service And Maintenance Instructions

Single-stage, non-communicating, 25-speed, ecm multipoise, condensing gas furnace with intelisense technology

Advertisement

Quick Links

59SP6B
Single-Stage, Non-Communicating, 25-Speed,
ECM Multipoise, Condensing Gas Furnace
with InteliSenseā„¢ Technology
NOTE: Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS

IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 1 - Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2 - Minimum Clearances to Combustible Materials
for All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 3 - Loose Parts Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCE-
DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 8
Table 4 - Minimum Free Area Required for Each Combustion Air
Opening or Duct to Outdoors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 5 - Minimum Space Volumes for 100% Combustion, Ventila-
tion and Dilution Air from Outdoors . . . . . . . . . . . . . . . . . . . . . . . 9
CONDENSATE TRAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CONDENSATE DRAIN CONNECTION . . . . . . . . . . . . . . . . . . . . 13
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 6 - Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 18
FILTER ARANGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 7 - Filter Media Pressure Drop (Clean) Versus Airflow - in. w.c.
(Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 8 - Filter Media Pressure Drop (Clean) Versus Face Velocity-
in. w.c. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 - Air Filter Selection and Duct Sizing - In. (mm) . . . . . 21
Table 10 - Air Filter Located in Filter Cabinet . . . . . . . . . . . . . . 21
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 11 - Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . 23
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 12 - Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
INTELISENSEā„¢ TECHNOLOGY . . . . . . . . . . . . . . . . . . . . . . . . . 28
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 13 - Vent Termination Kit for Direct Vent
(2-pipe) Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 14 - Approved Combustion-Air and Vent Pipe, Fitting
and Cement Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 15 - Maximum Equivalent Vent Length - Ft. . . . . . . . . . . 41
Table 16 - Deductions from Maximum Equivalent Vent Length - Ft.
(M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 17 - Maximum Allowable Exposed Vent Lengths in Uncondi-
tioned Space Insulation Table - Ft. / M . . . . . . . . . . . . . . . . . . . . 44
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
on the referenced subject, which is represented only by the standard in its entirety.
Installation, Start-up, Operating,
Service and Maintenance Instructions
38.) . . . . . . . . . . . . . . . . . . . 28
Table 18 - Hanger Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
AIR DELIVERY - CFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 19 - Air Delivery - CFM (with filter) . . . . . . . . . . . . . . . . 49
Table 20 - Default Airflow Settings . . . . . . . . . . . . . . . . . . . . . . 53
AND NAVIGATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 21 - System Status Display Codes . . . . . . . . . . . . . . . . . . 53
Table 22 - Main Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . 54
SERVICE LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 23 - Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 24 - Altitude Derate Multiplier for USA. . . . . . . . . . . . . . 59
Table 25 - Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 60
Table 26 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 62
ELECTRICAL CONTROLS AND WIRING . . . . . . . . . . . . . . . . . 63
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
WINTERIZATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
GAS FURNACE CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 76
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
TRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
To learn more about this appliance and installation via a mobile device,
go to
https://carrier.hvacpartners.com/NFC
access airflow tables or troubleshooting guide on your mobile device go
to
mlctraining.com/training/techdocs/92
To learn more about InteliSense, go to
or use the QR code below.
Mobile App QR Code
or use the QR code below. To
or use the QR code below.
Carrier.hvacpartners.com/InteliSense
Airflow QR Code

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 59SP6B and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier 59SP6B

  • Page 1: Table Of Contents

    59SP6B Single-Stage, Non-Communicating, 25-Speed, ECM Multipoise, Condensing Gas Furnace with InteliSense™ Technology Installation, Start-up, Operating, Service and Maintenance Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS Table 18 – Hanger Spacing ......46 IMPORTANT .
  • Page 2: Required Notice For Massachusetts Installations

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA-54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a.
  • Page 3 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A210796 Fig. 1 – Dimensional Drawing Table 1 – Dimensions SHIP WT. FURNACE SIZE LB (KG) CABINET WIDTH OUTLET WIDTH BOTTOM INLET WIDTH AIR INTAKE 040V14--10 14-3/16 (361) 12-1/2 (319) 12-9/16 (322) 7-1/8 (181) 124 (56.2)
  • Page 4: Safety Considerations

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions SAFETY CONSIDERATIONS WARNING WARNING FIRE, INJURY, OR DEATH HAZARD Failure to follow this warning could result in property damage, personal FIRE, INJURY, OR DEATH HAZARD injury, or death. Failure to follow this warning could result in property damage, personal Do not bypass any of the safety controls in the furnace, including but injury, or death.
  • Page 5: For All Units

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 13. These furnaces SHALL NOT be installed directly on carpeting, This is the safety-alert symbol . When you see this symbol on the combustible tile, or any other combustible material other than wood furnace and in instructions or manuals, be alert to the potential for flooring.
  • Page 6: Codes And Standards

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. None of the furnace model sizes can be used if the heating load is 20,000 BTU or lower.
  • Page 7: Dure

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions American Gas Association, 400 N. Capitol, N.W., Washington DC 3. After touching the chassis, you may proceed to service the control 20001 or connecting wires as long as you do nothing to recharge your body with static electricity (for example;...
  • Page 8: Air For Combustion And Ventilation

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions AIR FOR COMBUSTION AND VENTILATION CAUTION Introduction Direct Vent (2-pipe) Applications PERSONAL INJURY AND/OR PROPERTY DAMAGE When the furnace is installed as a direct vent (2-pipe) furnace, no special HAZARD provisions for air for combustion are required. However, other gas...
  • Page 9 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions The requirements for combustion and ventilation air depend upon Fig. 6 illustrates how to provide TWO OUTDOOR OPENINGS, whether or not the furnace is located in a space having a volume of at...
  • Page 10 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death. Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases.
  • Page 11: Condensate Trap

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 2. An attic or crawlspace may be considered a space that freely To Relocate the Condensate Trap: communicates with the outdoors provided there are adequate • Orient the furnace in the downflow position.
  • Page 12 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A230046 A230049 Fig. 11 – Horizontal Left Configuration (Appearance may vary) To Relocate the Condensate Trap: • Remove the knockout or plug in the casing for the condensate trap. • Install the grommet in the casing when required for direct-vent horizontal applications.
  • Page 13: Condensate Drain Connection

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions CONDENSATE DRAIN CONNECTION CAUTION PROPERTY DAMAGE HAZARD Failure to follow this caution may result in burst water pipes and/or property damage. If a condensate pump is installed, a plugged condensate drain or a failed pump may cause the furnace to shut down.
  • Page 14 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions For Right Side Condensate Drain: CAUTION 1. Remove the 7/8-in. knockout or plug from the right side of the casing. See Fig. 15 for suggested knockout or plug removal CUT HAZARD technique.
  • Page 15 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions condensate and compatible with mineral and vegetable oils, such as canola oil. Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line.
  • Page 16: Installation

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A10493 Fig. 20 – Duct Flanges A230007 Return Air Connections Fig. 18 – Horizontal Drain Trap Grommet WARNING INSTALLATION NOTICE FIRE HAZARD A failure to follow this warning could cause personal injury, death This furnace is certified to leak 2% or less of nominal air conditioning and/or property damage.
  • Page 17 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Supply Air Connections NOTE: For downflow applications, this furnace is approved for use on combustible flooring when any one of the following accessories are used: HORIZONTAL TOP RETURN NOT PERMITTED FOR ANY MODEL •...
  • Page 18 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions the heat exchanger can be viewed for possible openings using light CAUTION assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks. MINOR PROPERTY HAZARD Connect supply-air duct to flanges on furnace supply-air outlet.
  • Page 19: Filter Arangement

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions FILTER ARANGEMENT WARNING FIRE, CARBON MONOXIDE AND POISONING HAZARD Failure to follow this warning could result in fire, personal injury or death. Never operate a furnace without a filter or filtration device installed.
  • Page 20 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 7 – Filter Media Pressure Drop (Clean) Versus Airflow - in. w.c. (Pa) Representative After-Market Filter Media 14 x 25 Filter Factory-Accessory Factory-Accessory (356 x 635 mm) Washable Media Fiberglass Pleated (1-in.
  • Page 21 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 9 – Air Filter Selection and Duct Sizing - In. (mm) FURNACE FILTER SIZE FILTER CASING BOTTOM 4-in. † SIDE RETURN TYPE 21-in. Furnace Block Off 14-3/16 and 17-1/2-in. RETURN WIDTH...
  • Page 22: Air Ducts

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended from the floor joists, the ground underneath furnace COMBUSTION - AIR PIPE must be level and the furnace set on blocks or bricks.
  • Page 23: Gas Piping

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts. NOTE: For horizontal applications, the top most flange may be bent past 90_ to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.
  • Page 24: Electrical Connections

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions PRESSURE TESTING ABOVE ½ psig: pressure test. If test pressure is equal to or less than 0.5 psig (14-in. w.c.), turn off electric shutoff switch located on furnace gas control valve and The furnace and it’s individual shut-off valve must be disconnected from...
  • Page 25 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions WARNING WARNING ELECTRICAL SHOCK AND FIRE HAZARD FIRE HAZARD Failure to follow this warning could result in personal injury, death, or Failure to follow this warning could result in personal injury, death, or property damage.
  • Page 26 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Canada Installations: Make all electrical connections in accordance with the current edition of the Canadian Electrical Code CSA C22.1 and any local codes or ordinances that might apply. Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace.
  • Page 27 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 7. Install the green ground screw to the J-Box bracket and attach both ground wires to the green ground screw. 8. Connect any code required external disconnect(s) to field power wiring. 9. Connect field power and neutral leads to furnace power leads inside the external electrical box as shown in Fig.
  • Page 28: Intelisenseā„¢ Technology

    Alternate Power Supplies This furnace is designed to operate on utility generated power which has This furnace is InteliSense capable when used with an ecobee for Carrier a smooth sinusoidal waveform. If the furnace is to be operated on a smart thermostat with InteliSense technology.
  • Page 29: Venting

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 9. For Two-stage outdoor equipment, connection is Optional - See Cooling sequence of operations (adaptive mode) for additional information. If two-stage HP/cooling thermostat is connected to Y1 and Y/Y2 on Modulating or Two-stage furnace control board, Cooling Thermostat Type (Ctt) (setting on furnace control) should be set to “2St”...
  • Page 30: (2-Pipe) Systems

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions primers and cements from one manufacturer with a vent system from a raccords, ciments et apprêts conformes au ULC S636. La tuyauterie de ventilation des gaz, ses accessoires, le terminal concentrique mural different manufacturer.
  • Page 31: And Cement Materials

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 14 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials MATERIALS 1. All pipe*, fittings*, primers**, and solvents** must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards 2.
  • Page 32 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions the exhaust gases from one appliance from contaminating the WARNING combustion air of other gas appliances. Do not take combustion air from inside the chimney when using CARBON MONOXIDE POISONING HAZARD ventilated combustion air or single-pipe vent option.
  • Page 33 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions in the Air For Combustion and Ventilation Section. Do not use an pipe adapter on the furnace. See Fig. 49. This short inlet air pipe helps to abandoned chimney to supply outside air to the furnace. See Fig.
  • Page 34 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A12326 Fig. 42 – Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
  • Page 35 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A12325 Fig. 43 – Ventilated Combustion Air and Non-Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
  • Page 36 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A190032 Fig. 44 – Inside Corner Termination Inside Corner Terminations Inside corner vent terminations are permitted provided that: • Only two exterior walls come together to form an angle of 90 degrees to 135 degrees. There are no other exterior walls attached to either wall to form an alcove.
  • Page 37 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 1. Comply with all clearance requirements stated in Fig. 42 Fig. 43 WARNING per application. 2. Termination or termination kit should be positioned where vent CARBON MONOXIDE POISONING HAZARD vapors will not damage plants/shrubs, air conditioning equipment Failure to follow the instructions outlined below for each appliance or utility meters.
  • Page 38 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions a tight radius 2-in. (51 mm) 90 degree elbow is required to be attached to Refer to Fig. 49 for terminations approved for use in Alberta and the furnace. See Fig. 49. This short inlet air pipe helps to ensure stable Saskatchewan.
  • Page 39 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A93034 Fig. 50 – Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration Recommended Combustion Air Inlet Moisture Trap NOTICE OPTIONAL CONFIGURATION FOR COMBUSTION AIR INLET PIPE In applications where there is a risk of excessive moisture entering the...
  • Page 40 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 4. If a Tee is used on the termination (Alberta and Saskatchewan, when required) record the equivalent length of the Tee used. 5. Calculate Total Equivalent Vent Length by adding the equivalent lengths of the fittings to the lengths of the individual vent and combustion air pipes.
  • Page 41 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 15 – Maximum Equivalent Vent Length - Ft. NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Use Table 16 Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
  • Page 42 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Combustion Air and Vent Piping Insulation Guidelines NOTE: Use closed cell, neoprene insulation or equivalent. The vent pipe may pass through unconditioned areas. The amount of exposed pipe allowed is shown in Table 1.
  • Page 43 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A11327A HORIZONTAL LEFT-VERTICAL VENT CONFIGURATION A230011 UPFLOW VERTICAL VENT Fig. 54 – Upflow Configuration (Appearance May Vary) See “Notes for Venting Options” A11328A HORIZONAL LEFT-LEFT VENT CONFIGURATION A11311A DOWNFLOW LEFT CONFIGURATION A11329A...
  • Page 44 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions ALTERNATE COMBUSTION AIR CONNECTIONS A11335 Fig. 57 – Horizontal Right (Appearance May Vary) See “Notes for Venting Options” Notes for venting options Requires Internal Vent Kit See Product Data for Current Kit Number 1.
  • Page 45 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Maximum Allowable Exposed Vent Length in Unconditioned Space (Metric) 40,000* BTUH 60,000 BTUH Unit Size 3/8-in. 1/2-in. Uninsulated Uninsulated 3/8-in. Insulation 1/2-in. Insulation Insulation Insulation Winter Pipe Dia. Design Temp 6.1 15.2 13.7 6.1 18.3 15.2...
  • Page 46 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 14. Wipe excess cement from joint. A continuous bead of cement will WARNING be visible around perimeter of a properly made joint. 15. Handle pipe joints carefully until cement sets. CARBON MONOXIDE POISONING HAZARD 16.
  • Page 47 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Concentric Vent 2-Pipe and 1-Pipe Vent Termination Single or multiple concentric vent must be installed as shown in Fig. NOTE: Follow the instructions of the vent terminal manufacturer. These Maintain the required separation distance between vents or pairs of vents instructions are provided as a reference, only.
  • Page 48 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Venting System Length Calculations The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of elbows used in the venting system from Table Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
  • Page 49: Air Delivery - Cfm

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions AIR DELIVERY - CFM Table 19 – Air Delivery - CFM (with filter) Airflow External Static Pressure (in. w.c.) Unit Size Default Setting Setting Cont. Fan 040V14--10 Heating Low Cooling 1035 1010...
  • Page 50 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 19 – Air Delivery - CFM (with filter) (Continued) Airflow External Static Pressure (in. w.c.) Unit Size Default Setting Setting Cont. Fan 060V14--12 Heating/ Low Cooling 1035 1005 1055 1025 1090...
  • Page 51 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 19 – Air Delivery - CFM (with filter) (Continued) Airflow External Static Pressure (in. w.c.) Unit Size Default Setting Setting Cont. Fan 1015 1050 1005 1075 1035 1150 1110 1075 1035...
  • Page 52 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 19 – Air Delivery - CFM (with filter) (Continued) Airflow External Static Pressure (in. w.c.) Unit Size Default Setting Setting Cont. Fan 1025 1130 1065 1000 1225 1165 1105 1045 1310...
  • Page 53: Furnace Control Programming

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 20 – Default Airflow Settings Designated Airflow Settings Default Airflow Settings Unit Size Heating High Cooling Low Cooling Heating Const. Fan 040V14--10 (9 - 15) (1 - 3) 040V17--12 (5 - 10)
  • Page 54 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 22 – Main Menu Options Display Menu Item Idle/Stand by Mode ,... Displays the current furnace operating mode or active fault code. Faults code menu stores the 7 latest faults in memory. If no faults, None (...
  • Page 55: Service Label

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A221506 Fig. 59 – 3 Digit Display Flow Chart SERVICE LABEL A230314 Fig. 60 – Service Label Information Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 56: Start-Up, Adjustment, And Safety Check

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions START-UP, ADJUSTMENT, AND SAFETY CAUTION CHECK General CUT HAZARD Failure to follow this caution may result in personal injury. CAUTION Sheet metal parts may have sharp edges or burrs. Use care and wear...
  • Page 57: Wiring Diagram

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions WIRING DIAGRAM A221529 Fig. 61 – Wiring Diagram Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 58: Adjustments

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Prime Condensate Trap with Water WARNING WARNING FIRE OR EXPLOSION HAZARD CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Failure to follow these warnings could result in personal injury or death.
  • Page 59 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Heating value = 1050 Btu/cu ft. NOTICE Specific gravity = 0.62 Therefore: Orifice No. 44 The NATURAL GAS manifold pressure adjustments in Table 26 * Furnace is shipped with No. 44 orifices. In this example, all main compensate for BOTH altitude AND gas heating value.
  • Page 60 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions g. Jumper R and W thermostat connections on control to start Table 25 – Gas Rate (CU ft./hr) furnace, see Fig. SIZE OF TEST DIAL SIZE OF TEST DIAL SEC. SEC. h. Remove regulator adjustment cap from gas valve pressure...
  • Page 61 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Table 26 – Orifice Size and Manifold Pressure (in. w.c.) for Gas a. Turn gas valve ON/OFF switch to OFF. Input Rate b. Remove water column manometer or similar device from manifold pressure tap.
  • Page 62: Service And Maintenance Procedures

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 6. Allow the supply temperature to stabilize and verify the proper rise d. Set thermostat to “call for heat” and wait 1 minute. When the range. pressure switches are functioning properly, hot surface igniter...
  • Page 63: Electrical Controls And Wiring

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions digit being the number of long flashes. The major status code is WARNING displayed in the first 2 digits of the display. The minor status code is displayed in the third digit.
  • Page 64 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions internal filter with this furnace. See “Filter Arrangement” under the WARNING “Installation” section of this manual. NOTE: If the filter has an airflow direction arrow, the arrow must point ELECTRICAL SHOCK AND FIRE HAZARD toward the blower.
  • Page 65 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions f. After servicing the blower, reverse steps a through e, resealing combustion air pipe per installation instructions. g. Tighten all clamps 15 lb -in. Fig. 66 For Steps 5 through 14. TORQUE THE BLOWER WHEEL SET SCREW 5.
  • Page 66 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions b. Verify blower is rotating in the correct direction 14. Remove wires from both rollout switches. 18. If furnace is operating properly, RELEASE BLOWER DOOR 15. Slide one-piece burner out of slots on sides of burner assembly.
  • Page 67 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions Flushing Collector Box and Drainage System WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service.
  • Page 68 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 13. Clean port on collector box with a small wire. WARNING To re-install Condensate Drain and Trap: 1. Remove adhesive backing from condensate trap gasket ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD 2. Install gasket on collector box Failure to follow this warning could result in personal injury or death, 3.
  • Page 69: Winterization

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions 10. Repeat Steps 5 through 8. WARNING 11. If a condensate pump is used, check with pump manufacturer to verify pump is safe for use with antifreeze used. Allow pump to FIRE OR EXPLOSION HAZARD start and pump anti-freeze to open drain.
  • Page 70 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions is energized. When the thermostat is satisfied, the R-to-G-and-Y circuit are opened. Simultaneously, the electronic air cleaner terminal EAC-1 is The outdoor unit stops, and the furnace blower BLWM and electronic air...
  • Page 71 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions When the thermostat “calls for low-cooling”, the blower motor BLWM will switch to operate at low-cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at low-cooling airflow before transitioning back to continuous-blower airflow.
  • Page 72: Troubleshooting

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions TROUBLESHOOTING A221600 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 73 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A221601 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 74 59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions A221602 Fig. 71 – Troubleshooting Guide Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 75: Gas Furnace Checklist

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions GAS FURNACE CHECKLIST GAS FURNACE CHECKLIST Installation Date: ____________________________ Furnace Thermostat Humidifier Indoor Coil Outdoor Unit Furnace Location_____________________________ Furnace Orientation: ____Upflow Gas Adjustment LOCAL GAS HEAT CONTENT_____________(btu/cu. ft.) (contact your local gas utility-not required for propane) INLET SUPPLY PRESSURE** MANIFOLD PRESSURE: High fire___________ in.
  • Page 76: Parts Replacement Information Guide

    59SP6B: Installation, Start-up, Operating, Service and Maintenance Instructions PARTS REPLACEMENT INFORMATION GUIDE Casing Group Media Cabinet (when used) Gas Control Group Blower door Bottom plate Burner Control door Flame sensor Door knob assembly Gas valve Top filler plate Hot surface igniter...

Table of Contents