Condensate Drain Connection - Carrier 59SP6A Installation, Start-Up, Operating, Service And Maintenance Instructions

Single-stage, non-communicating, variable-speed, ecm multipoise, condensing gas furnace
Table of Contents

Advertisement

59SP6A: Installation, Start-up, Operating, Service and Maintenance Instructions
5
If alternate vent position
is required, loosen clamp
on vent elbow inlet.
Remove relief tube
from port on collector
box.
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Left Orientation
NOTE: Remove knockout in
casing before re-installing the
condensate trap.
Rotate elbow to
9
desired position
and torque clamp
on inlet 15 lb.-in.
Slide relief tube in
stand-offs to adjust
length.
Attach condensate
trap with screw to
collector box.
Align trap over middle
and right-hand port on
collector box.
Horizontal Left Trap Configuration
Fig. 11 – Horizontal Left Configuration
(Appearance may vary)
Air gap here
Open standpipe
for coil or
humidifier drain
TEE
(1/2" CPVC to 3/4" PVC
adapter from loose parts bag.)
Evaporator Coil
+
+
Open standpipe
(Optional when coil drain is
not connected to furnace
3/4" PVC
+
drain.)
+
+
3/4
+
Condensing
+
3/4" PVC
3/4
Furnace
+
+
+
+
+
3/4
1/2" CPVC or larger*
Recommend "T" fitting
< +
standpipe of same
< +
< +
diameteror larger
3/4
Blower
3/4
+ = Positive pressure
< + = Pressure lower than areas with +
( = Negative pressure
Fig. 12 – Example of Field Drain Attachment
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Remove the screw that secures the
condensate trap to the collector box
and remove trap.
Remove relief tube from
relief port on condensate
trap.
Remove front pressure
switch tube and discard.
A new tube is shipped in
the Loose Parts bag.
Remove middle and right
6
plug from collector box.
DO NOT DISCARD.
Install two plugs previously
removed in open ports on
collector box.
Connect relief tube to port
on collector box.
Connect the new pressure switch
7
tube from Loose Parts bag to port
on front pressure switch.
Route pressure switch tube
8
underneath relief tube and
connect to port on
collector box.
Connect relief tube to relief
port on condensate trap.
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Evaporator Coil
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
+ + +
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
3/4" PVC
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
+
+
3/4
+
Ä Ä Ä Ä Ä Ä Ä Ä Ä Ä
3/4" PVC
Condensing
3/4
+
+
Furnace
Open standpipe
+
+
Air gap required when
another drain is connected
+
to furnace drain.
+
3/4
TEE
(1/2" CPVC to 3/4" PVC
< +
adapter from loose parts bag.)
< +
< +
-
3/4
Blower
-
-
- -
3/4
To open drain
-
+ = Positive pressure
< + = Pressure lower than areas with +
= Negative pressure
Ä Ä Ä Ä Ä Ä Ä Ä Ä
Evaporator
Coil
+
Ä Ä Ä Ä Ä Ä Ä Ä Ä
+
Open standpipe
Ä Ä Ä Ä Ä Ä Ä Ä Ä
(Optional when coil drain is
3/4" PVC
Ä Ä Ä Ä Ä Ä Ä Ä Ä
+
not connected to furnace
Ä Ä Ä Ä Ä Ä Ä Ä Ä
drain.)
3/4
Ä Ä Ä Ä Ä Ä Ä Ä Ä
+
+
3/4
Ä Ä Ä Ä Ä Ä Ä Ä Ä
Condensing
3/4
+
Furnace
+
3/4" PVC
+
TEE
3/4
(1/2" CPVC to 3/4" PVC
high
adapter from loose parts bag.)
< +
< +
< +
-
3/4
Blower
-
-
- -
3/4
-
+ = Positive pressure
< + = Pressure lower than areas with +
= Negative pressure
Evaporator Coil
+
+
+
Condensing
Furnace
+
+
+
Blower
-
- -
-
+ = Positive pressure
< + = Pressure lower than areas with +
− = Negative pressure
Fig. 13 – Example of Field Drain Attachment (Not Allowed)

CONDENSATE DRAIN CONNECTION

FROZEN AND BURST WATER PIPE HAZARD
Failure to protect against the risk of freezing may result in property
A11574
damage.
Special precautions MUST be made if installing furnace in an area
which may drop below freezing. This can cause improper operation or
damage to equipment. If furnace environment has the potential of
freezing, the drain trap and drain line must be protected. The use of
accessory drain trap heaters, electric heat tape and/or RV antifreeze is
required for these installations.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in burst water pipes and/or
property damage.
If a condensate pump is installed, a plugged condensate drain or a failed
pump may cause the furnace to shut down. Do not leave the home
unattended during freezing weather without turning off water supply
and draining water pipes or otherwise protecting against the risk of
frozen pipes.
DO NOT trap the drain line in any other location than at the condensate
drain trap supplied with the furnace. If possible, DO NOT route the drain
line where it may freeze. The drain line must terminate at an inside drain
to prevent freezing of the condensate and possible property damage.
Special precautions MUST be made if installing furnace in an area
A170135
which may drop below 32°F (0°C). This can cause improper operation or
damage to the equipment. If the furnace environment has the potential of
freezing, the drain trap and drain line must be protected. In areas where
the temperature may be below 32°F (0°C), a Condensate Freeze
Protection kit is strongly recommended. The kit includes a condensate
12
Evaporator Coil
+ + +
+ = Positive pressure
< + = Pressure lower than areas with +
+
+
+
− = Negative pressure
Condensing
Furnace
+
+
+
Blower creates positive pressure.
+
Positive pressure extends into coil
+
condensate drain (no trap).
< +
< +
< +
Furnace condensate does not flow
consistently when drain is at positive
-
+
pressure.
Blower
-
+
-
- -
+
-
+
Evaporator Coil
+
+
Open
standpipe
3/4" PVC
+
+
+
+
3/4
+
Condensing
+
3/4" PVC
Furnace
3/4
+
+
+
+
3/4
1/2" CPVC or larger*
+
< +
< +
< +
3/4
-
1/2
+
Blower
-
-
1/2
- -
+
-
3/4
+ = Positive pressure
< + = Pressure lower than areas with +
− = Negative pressure
CAUTION
!
CAUTION
!
3/4" PVC
+
+
3/4
+
+
3/4" PVC
3/4
+
+
3/4
1/2" CPVC or larger*
+
+
< +
3/4
< +
< +
+
+
-
+
+
3/4
-
+
+
+
3/4
+
A14532

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents