Macurco OX-6 User Instructions page 14

Oxygen detector, controller and transducer
Hide thumbs Also See for OX-6:
Table of Contents

Advertisement

Available languages

Available languages

Selecting Fan Relay Settings – "FrS"
To select the Fan Relay setting, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push the Enter
button to enter the Con menu. The seventh selection is the "FrS" or Fan Relay setting. Push Next six times to get to "FrS" then Enter.
If the fan relay is "dIS" (disabled) push Next to change it to 18, 18.1, 18.2, 18.3, 18.4, 18.5, 18.6, 18.7, 18.8, 18.9, 19, 19.1, 19.2, 19.3,
19.4, 19.5, 19.6, 19.7, 19.8, 19.9, 20, 20.1, 20.2, 20.3, 20.4 or 20.5% v/v (flashing) then push Enter to confirm the change (solid) and
push Enter again to return to "FrS" in the Con menu. Push Next until "End" is displayed then push Enter to get back to normal
operation.
Selecting Fan Relay Delay – "Frd"
To select the Fan Relay Delay setting, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push the
Enter button to enter the Con menu. The eighth selection is the "Frd" or Fan Relay Delay. Push Next seven times to get to "Frd" then
Enter. If the delay is "0" (disabled) push Next to change it to 1, 3, 5, or 10 minutes (flashing) then push Enter to confirm the change
(solid) and push Enter again to return to "Frd" in the Con menu. Push Next until "End" is displayed then push Enter to get back to
normal operation.
Selecting Fan Relay Run Time – "Frr"
To select the Fan Minimum Runtime setting, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then
push the Enter button to enter the Con menu. The ninth selection is the "Frr" or Fan Minimum Run Time. Push Next eight times to get
to "Frr" then Enter. If the runtime is "OFF" (disabled) push Next to change it to 3, 5, 10 or 15 minutes (flashing) then push Enter to
confirm the change (solid) and push Enter again to return to "Frr" in the Con menu. Push Next until "End" is displayed then push Enter
to get back to normal operation.
Selecting Fan Relay Latching Option – "FrL"
To select the Fan Relay Latching Option, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push
the Enter button to enter the Con menu. The tenth selection is the "FrL" or Fan Relay Latching Option. Push Next nine times to get to
"FrL" then Enter. If latching is "OFF" push Next to turn it to "On" (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to "FrL" in the Con menu. Push Next until "End" is displayed then push Enter to get back to normal operation.
Selecting Trouble Fan Setting Option – "tFS"
To select the Trouble Fan Setting Option, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then
push the Enter button to enter the Con menu. The eleventh selection is the "tFS" or Trouble Fan Setting Option. Push Next ten times
to get to "tFS" then Enter. If Trouble Fan Setting is "OFF" push Next to turn it to "On" (flashing) then push Enter to confirm the change
(solid) and push Enter again to return to "tFS" in the Con menu. Push Next until "End" is displayed then push Enter to get back to
normal operation.
Selecting 4-20mA Output Option – "420"
To select the 4-20mA Output Option, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push the
Enter button to enter the Con menu. The twelfth selection is the "420" or 4-20mA Output Option. Push Next eleven times to get to
"420" then Enter. If the 4-20mA is "On" push Next to turn it to "OFF" (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to "420" in the Con menu. Push Next until "End" is displayed then push Enter to get back to normal operation.