Default - Factory Settings - Macurco OX-6 User Instructions

Oxygen detector, controller and transducer
Hide thumbs Also See for OX-6:
Table of Contents

Advertisement

Available languages

Available languages

3.
With the 4-20 mA function turned "On" and the O2 concentration climbing the 4-20 mA signal will ramp up corresponding to the
concentration (0-25% v/v).
Default Configuration – Factory Settings
The default Power Up Test setting is ON
The default Display setting is ON
The default Buzzer setting is ON
The default Alarm Relay Setting is activation at 19.5% v/v
The default Alarm Relay Configuration is Normally Open
The default Fan Relay Setting is activation at 20.2% v/v
The default Fan Relay Delay setting is 3 minutes
The default Fan Relay Runtime setting is 0 minutes
The default Fan Relay Latching condition is OFF
The default Trouble Fan Setting condition is OFF
The default 4-20mA Output setting is ON
To change settings, remove the Philips screw on the front of the OX-6. Pull off the front cover of the unit.
12