Scope Of Application - Panasonic OCU-CR1001VF Installation Instructions Manual

Outdoor type refrigeration unit
Table of Contents

Advertisement

Scope of Application

This refrigeration unit operates with a rotary compressor.
Use the refrigeration unit within the range shown below.
Item
Refrigerant
Evaporating temperature
Suction pressure
Inverter operation
Suction gas temperature
Superheat at suction
Discharge pressure
Discharge gas temperature
Oil temperature
Ambient temperature
Applied electricity
Unbalance of phase voltage
Installation inclination angle
ON/OFF cycle period
Installation
Note ※: Operation may not be possible depending on the installed condition.
Counter measures in a cold weather operation
In order to prevent excessive reduction of high pressure in a cold weather location, surrounding around the refrigeration
unit should be made.
Standard Value
R744
-45°C to -5°C
0.73MPa to 2.95MPa
30 s
-1
to 60 s
-1
18°C or below
10 K or above
9.1MPa or below
(except transient)
97°C or below
100°C or below
(Ambient temperature +10 K or above)
-15°C to +43°C
3 phase 200 V ± 20 V
2% or below
1° or below
10 minutes or longer
for ON/OFF cycle
Outdoor
Remarks
The charge supply amount shall be adequate.
Temperature conversion of inlet pressure
Unit inlet pressure
Unit inlet (suction gas) pipe temperature
Difference between evaporating temperature
and compressor inlet temperature
Compressor outlet pressure
Compressor outlet temperature
Gas cooler intake air temperature
Power source terminal voltage
on Refrigeration unit
Oil return shall be ensured.
The foundation shall be rigid enough.
8