Installation Example

Standard installation
The gas cooler is designed to take air from 3 directions,
including the front, left and right side, and blow out from
the top.
(1) Secure a service space of 500 mm or more on the
front and left sides.
(2) Secure a service space of 300 mm or more on the
back and right sides.
Back surface
suction space
Front surface
500mm
service space
Installation example
When a wall exists on one side
500 mm or
wider
Front surface
service space
500 mm or
wider
Front surface
service space
Continuous installation
500 mm or
wider
Front surface
service space
300
mm
When a wall exists on two sides
500 mm or
wider
Front surface
service space
300 mm or wider
500 mm or
wider
Front surface
service space
500 mm or
wider
Front surface
service space
When there's an obstacle in the upward
direction
When there's an obstacle in the
upward direction, the installation
should not cause a short cycle of
the gas cooler air exhaust.
When installing a roof, it should be
located at a distance of 1.5 m or
more with an upward slope, as
illustrated on the right.
Protection in the snowfall areas
(1) Install a snow protection shed at the air outlet of the
gas cooler. (On-site installation)
(2) The entire refrigeration unit should not be surrounded
by accumulated snow.
When a wall exists on three sides
300 mm or wider
500 mm or
wider
Front surface
service space
When a wall exists on four sides
500 mm or wider
500 mm or
wider
Front surface
service space
Notes: 1. Provide an air suction opening of 4 m
or greater at the lower part.
2. The wall height must be up to the unit
height.
2
14