Troubleshooting - Bryant EVOLUTION V Installation Instructions Manual

Variable speed air conditioner
Table of Contents

Advertisement

NOTE: The unit may be operated with an Evolution Connex
Control or a standard 2- -stage thermostat. Evolution Connex
Control will utilize 5 stages cooling, while 2- -stage thermostat will
only allow 2 discrete stages of cooling operation.
Variable Speed Compressor
This unit contains a variable speed rotary compressor that has a
wide operating range. It operates on a variable 3 phase sine wave
provided by the inverter. This compressor can only be operated by
the specific inverter supplied with the unit.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
and/or improper operation.
Do not attempt to apply line voltage directly to the
compressor. This will destroy the compressor.
Field control Connections
For communicating operation use the communication Evolution
plug only. Only two wires, AB (color), are required. If necessary,
connect C for additional grounding (see Fig. 6). If using standard
2- -stage thermostat, connect discrete inputs (R,C,Y2,Y1) for
2- -stage control in cooling modes.
Pressure Transducer (SPT)
A 5 VDC output low pressure transducer that provides a 0- -5 VDC
data for interpretation by the control board for a 0 to 200 psig
range of pressure at the suction tube. This interpreted pressure data
is then intelligently used by the AOC control board for low
pressure cut- -out, loss of charge management, compressor
protection,
oil
circulation
management.
Pressure Equalizer Valve (PEV)
At the end of every compressor operation (after the 3.5 minute
Time Guard period), the equalizer valve opens for 150 seconds
plus an additional 15 seconds of protection before allowing the
compressor to start ramping up.
The PEV is located next to the suction and discharge of the
compressor.
The function of this valve is to prevent the
compressor from starting with a high refrigerant pressure
differential, thus helping the reliability of the compressor.
NOTE: A hissing sound may be heard during the equalization
process. This is normal.
management,
and
lubrication

TROUBLESHOOTING

Systems Communication Failure
If communication is lost with the User Interface (UI), the control
will flash the appropriate fault code (see Table 6). Check the wiring
to the User Interface and the indoor and outdoor units and power.
Model Plug
Each control board contains a model plug. The correct model plug
must be installed for the system to operate properly (see Table 3).
The model plug is used to identify the type and size of unit to the
control.
On new units, the model and serial numbers are inputted into the
AOC board's memory at the factory. If a model plug is lost or
missing at initial installation, the unit will operate according to the
information input at the factory and the appropriate error code will
flash temporarily. An RCD replacement AOC board contains no
model and serial information. If the factory control board fails, the
model plug must be transferred from the original board to the
replacement board for the unit to operate.
When installing AC unit with older fan coils, a model plug change
may be required.
NOTE:
The model plug takes priority over factory model
information input at the factory. If the model plug is removed after
initial power up, the unit will operate according to the last valid
model plug installed, and flash the appropriate fault code
temporarily.
Table 3 – Factory Supplied Model Plug Information
MODEL PLUG
189BNV0
NUMBER
13
HK70EZ028
25
HK70EZ011
24B
HK70EZ010
36
HK70EZ012
37
HK70EZ025
48
HK70EZ013
49
HK70EZ027
60
HK70EZ014
Service Tool
Fig. 27 - - Service Tool Connection
When working on the outdoor unit of a split system, the technician
would usually need to repeatedly walk between the indoor wall
control and the unit outside. To save time, the communicating
controls offer a service tool feature.
By wiring the service tool into the AOC board and powering it
with an external adapter, the technician can have a wall control
capable of running the system right at the outdoor unit.
14
PIN RESISTANCE
(K--- ohms)
Pins 1--- 4
Pins 2--- 3
11K
180K
5.1K
150K
5.1K
120K
5.1K
180K
11K
91K
5.1K
220K
11K
150K
5.1K
270K
A150062

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

189bnv

Table of Contents