Type
98
Local
down and when stage is at
lowest level, will elevate to
HIGH TORQUE LOCKOUT
System
(Elevated from fault code
99
Malfunction
98 when 98 occurs at low-
Reset
Amber LED Description
Time
HIGH TORQUE EVENT
(Event will cause stage
NA
fault code 99)
2 hours
est stage)
Mode
Possible Causes
Both
Refer to 99
Both
Miswire
Refrigerant over-
Both
charge
Check ODU coil for clogging (ice or de-
Outdoor Airflow too
bris) and clean if necessary; Troubleshoot
Both
ODU fan motor and make sure it is work-
low or off
Expansion Device
Both
Restriction
25
Actions
Refer to 99
Check miswire of compressor leads at
terminals U,V,W
Check refrigerant amount
ing
Troubleshoot TXV
Troubleshoot EXV