Honeywell Aquastat L4006 Installation Manual page 6

Hide thumbs Also See for Aquastat L4006:
Table of Contents

Advertisement

Installation Guide
SPECIFICATIONS
Table 2. L6006, L6007, L6008 Controller (SPDT Switching) Specifications.
Model
Application
L6006A
Circulator and
low limit or high
limit
L6006B
Circulator and
low limit or high
limit
L6006C
Circulator, low
limit, and high
limit
L6007A
Circulator and
low limit or high
limit
L6008A
Circulator and
low limit cooling
L6008G
Two-stage
Aquastat
Controller to
cycle two-stage
gas valve.
L6008H
Low fire Aquastat
(maximum
Controller
temperature
of element
405° F
(207° C))
a Some models include copper well or fitting; specify when ordering. Also specify boiler tapping size 1/2 or 3/4 in. NPT and
insulation depth.
60-2104—01
Range °F (°C)
Differential °F (°C)
100° F to 240° F
5° F (3° C) fixed
(38° C to 116° C)
or
or
5° F to 30° F
100° F to 290° F
(3° C to 17° C)
(38° C to 143° C)
adjustable
100° F to 240° F
5° F (3° C) fixed
(38° C to 116° C)
or
5° F to 30° F
(3° C to 17° C)
adjustable, or
30° F (17° C)
fixed.
65° F to 200° F
5° F (3° C) fixed
(18° C to 93° C)
or
5° F to 30° F
(3° C to 17° C)
adjustable
40° F to 180° F
Fixed
(4° C to 82° C)
100° F to 240° F
5° F (3° C) fixed
(38° C to 116° C)
or
or
5° F to 30° F
-30° F to +70° F
(3° C to 17° C)
(-35° C to +21° C)
adjustable
130° F to 230° F
3-1/2° F (2° C)
(54° C to 110° C)
fixed
or
60° F to 160° F
(16°
C to 71° C)
150° F to 200° F
15° F (8° C)
(66° C to 93° C)
fixed
Midscale
Insertiona
Horizontal
Horizontal
Horizontal or
vertical surface
mounted
Horizontal or
vertical
Remote bulb
Remote bulb
Remote bulb
4
Available Options
- SUPER TRADELINE model
available.
- Modified dial with stop.
- NPT brass spud 1/2 in. or
3/4
in. (13 mm to 19 mm)
- 3-3/8 in. (86 mm) insertion.
- Without well.
- Adapter for horizontal or
vertical mount.
- Insulation depth 1-1/2 in. or
3 in. (38 mm or 76 mm).
- Direct immersion.
- Insulation depth 1-1/2 in.
(38 mm).
- 3/4 in. (19 mm ) brass
compression fitting.
- TRADELINE model
available.
- Strap-on, surface mount.
- Insulation depth 1-1/2 in. or
3 in. (38 mm or 76 mm).
- TRADELINE models
available.
- Modified dial with stop.
- Capillary 5-1/2 ft (1.7 m).
- Capillary 6 ft (1.8 m).
- Adjustable interstage
differential; 5° F to 10° F
(2° C to 6° C).
- Capillary 33 in. (0.8 m).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents