Specifications - Honeywell Aquastat L4006 Installation Manual

Hide thumbs Also See for Aquastat L4006:
Table of Contents

Advertisement

IMPORTANT
The specifications given in this publication do
not include normal manufacturing tolerances.
Therefore, this unit may not exactly match the
listed specifications. Also, this product is tested
and calibrated under closely controlled conditions,
and some minor differences in performance can be
expected if those conditions are changed.
SUPER TRADELINE®/TRADELINE MODELS
SUPER TRADELINE controls offer features not available
on TRADELINE or standard models, and are designed
to replace a wide range of Honeywell and competitive
controls.
TRADELINE models are selected and packaged to
provide ease of stocking, ease of handling, and maximum
replacement value. Specifications of SUPER TRADELINE
and TRADELINE controls are the same as those of
standard models except as noted below.
SUPER TRADELINE Model: L6006A Aquastat Controller.
SUPER TRADELINE Features:
SUPER TRADELINE package with cross reference label
and special instructions.
Factory-set stop at 240° F (116° C).
Vertical or horizontal mount.
Tube of heat-conductive compound.
Insulation: 1-1/2 in. to 3 in. (38 mm to 76 mm).
TRADELINE Models: L4006A,B,E; L4008E; L6006C;
L6008A Aquastat Controllers.
TRADELINE Features Available:
TRADELINE package with cross reference label and spe-
cial instructions.
Some TRADELINE models include immersion well.
Factory-set stops at 180° F, 240° F, or 250° F (82° C, 116°
C, or 121° C).
Vertical or horizontal mount.
Tube of heat-conductive compound.
Insulation depths of 1-1/2 in. or 3 in. (38 or 76 mm).
Standard Models:
NOTE: The following specifications are standard. Variances,
available as options, are listed in Tables 1 and 2.
Electrical Ratings (A):
Models with 2° F (1° C) fixed differential:
120 Vac
Full Load
2.6
Locked Rotor 15.6
Models with 5° F (3° C) fixed differential or 5° F to 30°F (3°
C to 17° C) adjustable differential:
110/120 Vac
Full Load
8.0
Locked Rotor 48.0
Millivoltage
0.25 at 0.25 to 12 Vdc
a
L6008G only.
Switching:
L4006, L4007, L4008: Spst.
L6006, L6007, L6008: Spdt (breaks R-B and makes R-W on
temperature rise at setpoint).
Pressure Rating:
Capillary Bulb (Direct Immersion): 200 psi (1379 kPa).
Immersion Well: 255 psi (1758 kPa).
Sensing Bulb Material: Copper.
Sensing Bulb Fill: Liquid toluene or silicone oil.
Sensing Bulb Dimensions: 2-7/8 in. (73 mm) long,
3/8 in. (10 mm) diameter.
Wiring: Screw terminals.
Maximum Ambient Temperature: 150° F (66° C)
1
Aquastat L4006,7,8;L6006,7,8

SPECIFICATIONS

240 Vac
1.3
7.8
200/240 Vac
277 Vac
5.1
4.2
30.6
25.2
60-2104—01
a

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents