Honeywell Aquastat L4006 Installation Manual page 13

Hide thumbs Also See for Aquastat L4006:
Table of Contents

Advertisement

INSERT BULB
IN CLAMP
OUTDOOR
SENSING
BULB
SEAL-OFF
TUBE
34886A
BULB
SHIELD
Fig. 15. Mounting bulb in shield outside building.
Mount L6008A Remote Bulb Controller
7
Mounting with Guard Bracket
Mount the bulb in the guard bracket as shown in
Fig. 16. Locate the bulb and bracket combination,
in freely circulating air, in the controlled area. With
screws provided, fasten the bracket in place
Mounting on Suction Line
1. In cooling units with more than one suction line,
place the sensing bulb on the common line.
2. Make certain the bulb is at least 2 ft (0.6
m) from the point at which the suction line
leaves the cooler. This prevents the outside
temperature from being transmitted to the
remote bulb through the copper tubing of the
suction line.
3. Place the remote sensing bulb on the side of
the horizontal suction line between the coil and
trap (not on the trap).
4. Attach the sensing bulb to the suction line with
clips or straps. (See Fig. 17). 5. Coil the excess
length of capillary tubing near the L6008A case.
5. Coil the excess length of capillary tubing near
the L6008A case.
SPLIT WOOD PLUG
3/4 IN.
(19 MM)
HOLE IN
WALL
CAPILLARY
TUBING
M8800B
Fig. 16. Securing remote bulb in clip.
COOLER
WALL
COIL
L6008A
CIRCULATOR
LOW LIMIT
CONTROLLER
CAPILLARY
REMOTE
BULB
Fig. 17. Attaching remote bulb to horizontal
Mount Surface Mount Models
8
The L4006H and L6006C are designed for sur-
face mounting on piping or tanks. Mount the
controller directly on the tank surface using the
adjustable mounting bracket as shown in Fig. 18.
The controller can be mounted in any position.
When mounting the L4006H or L6006C on pip-
ing, the pipe should be 1 in. (25 mm) diameter or
larger for accurate temperature sensing. Remove
any insulation from the pipe. Thoroughly scrape
off all scale, rust, or paint. Mount the control-
ler using adjustable bracket provided. Turn on
power..
11
Aquastat L4006,7,8;L6006,7,8
MOUNTING
SUPPORTING
CLIP
SENSOR
M8791A
SUCTION LINE
LEAVES
COOLER
SUCTION
LINE
BULB CLIPS
TO SUCTION LINE
M8805B
suctionline.
60-2104—01