Troubleshooting
Fault display
(cont.)
Deleting the fault codes from the fault memory
Press the following keys:
1.
+
simultaneously for approx. 4 s.
d
å
The "Service" menu appears.
2.
/
for "Fault history".
|
~
3.
to confirm.
d
Fault codes
Fault code dis-
System characteristics
played
20
Burner blocked
21
Return temperature raising
■
facility valve opening
Boiler circuit pump starts
■
22
Burner blocked
24
Control unit set to 0 °C out-
side temperature
25
No DHW heating
26
Control mode
27
Control mode
28
Control mode
29
Control mode
30
Burner blocked
31
Return temperature raising
■
facility valve opening
Boiler circuit pump starts
■
32
Burner blocked
34
Control unit set to 0 °C out-
side temperature
35
No DHW heating
36
Control mode
37
Control mode
38
Control mode
39
Control mode
70
4.
/
for "Delete".
|
~
5.
/
for "Yes".
|
~
6.
to confirm.
d
7.
until the default display is shown.
ä
Cause
Short circuit, boiler water
temperature sensor
Short circuit, boiler return
temperature sensor
Short circuit, flue gas tem-
perature sensor
Short circuit, outside tem-
perature sensor
Short circuit, top buffer
temperature sensor
Short circuit, buffer tem-
perature sensor 2
Short circuit, buffer tem-
perature sensor 3
Short circuit, buffer tem-
perature sensor 4
Short circuit, buffer tem-
perature sensor 5
Lead break, boiler flow
temperature sensor
Lead break, boiler return
temperature sensor
Lead break, flue gas tem-
perature sensor
Lead break, outside tem-
perature sensor
Lead break, buffer tem-
perature sensor 1 (top)
Lead break, buffer tem-
perature sensor 2
Lead break, buffer tem-
perature sensor 3
Lead break, buffer tem-
perature sensor 4
Lead break, buffer tem-
perature sensor 5
Measures
Check boiler water temperature
sensor.
Check boiler return temperature
sensor.
Check flue gas temperature sen-
sor.
Check outside temperature sensor.
Check top buffer temperature sen-
sor.
Check centre buffer temperature
sensor.
Check bottom buffer temperature
sensor.
Check bottom buffer temperature
sensor.
Check bottom buffer temperature
sensor.
Check boiler flow temperature sen-
sor.
Check boiler return temperature
sensor.
Check flue gas temperature sen-
sor.
Check outside temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.