Deleting The Fault Codes From The Fault Memory; Fault Codes - Viessmann Vitoligno 300-C Installation And Service Instructions For Contractors

Pellet boiler
Table of Contents

Advertisement

Troubleshooting
Fault display
(cont.)

Deleting the fault codes from the fault memory

Press the following keys:
1.
+
simultaneously for approx. 4 s.
d
å
The "Service" menu appears.
2.
/
for "Fault history".
|
~
3.
to confirm.
d

Fault codes

Fault code dis-
System characteristics
played
20
Burner blocked
21
Return temperature raising
facility valve opening
Boiler circuit pump starts
22
Burner blocked
24
Control unit set to 0 °C out-
side temperature
25
No DHW heating
26
Control mode
27
Control mode
28
Control mode
29
Control mode
30
Burner blocked
31
Return temperature raising
facility valve opening
Boiler circuit pump starts
32
Burner blocked
34
Control unit set to 0 °C out-
side temperature
35
No DHW heating
36
Control mode
37
Control mode
38
Control mode
39
Control mode
70
4.
/
for "Delete".
|
~
5.
/
for "Yes".
|
~
6.
to confirm.
d
7.
until the default display is shown.
ä
Cause
Short circuit, boiler water
temperature sensor
Short circuit, boiler return
temperature sensor
Short circuit, flue gas tem-
perature sensor
Short circuit, outside tem-
perature sensor
Short circuit, top buffer
temperature sensor
Short circuit, buffer tem-
perature sensor 2
Short circuit, buffer tem-
perature sensor 3
Short circuit, buffer tem-
perature sensor 4
Short circuit, buffer tem-
perature sensor 5
Lead break, boiler flow
temperature sensor
Lead break, boiler return
temperature sensor
Lead break, flue gas tem-
perature sensor
Lead break, outside tem-
perature sensor
Lead break, buffer tem-
perature sensor 1 (top)
Lead break, buffer tem-
perature sensor 2
Lead break, buffer tem-
perature sensor 3
Lead break, buffer tem-
perature sensor 4
Lead break, buffer tem-
perature sensor 5
Measures
Check boiler water temperature
sensor.
Check boiler return temperature
sensor.
Check flue gas temperature sen-
sor.
Check outside temperature sensor.
Check top buffer temperature sen-
sor.
Check centre buffer temperature
sensor.
Check bottom buffer temperature
sensor.
Check bottom buffer temperature
sensor.
Check bottom buffer temperature
sensor.
Check boiler flow temperature sen-
sor.
Check boiler return temperature
sensor.
Check flue gas temperature sen-
sor.
Check outside temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.
Check buffer temperature sensor.