Codes
Code 1
Call up code 1
Press the following keys:
1.
+
simultaneously for approx. 4 s.
d
å
The "Service" menu appears.
2.
/
for "Code 1".
|
~
3.
to confirm.
d
4.
/
for the required group.
|
~
5.
to confirm.
d
6.
/
for the required coding address.
|
~
7.
to confirm.
d
8.
/
for the required value.
|
~
9.
to confirm.
d
"Adopted" appears briefly in the dis-
play.
General
Coding
Coding in the delivered condition
Detached house/apartment building
7F:1
Detached house; same holiday
program for all heating circuits
Minimum temperature, top buffer sensor
91:0
No minimum temperature
Charging
Is available, if code "Charging scheme", Hardware
group, is selected.
Coding
Coding in the delivered condition
Feed screw conveyor, heat-up cycle
14:...
Start cycle of the feed screw con-
veyor, in % after boiler ignition.
Delivered condition for boiler out-
put:
8 and 12 kW: 20
18 to 48 kW: 40
50
10.
Exit the service menu.
ä
Overview
The coding addresses are displayed in groups, subject
to system configuration:
"General"
■
See page 50
■
"Charging"
See page 50
■
"Hardware"
See page 52
"Heating"
■
See page 54
"Boiler"
■
See page 56
■
"Buffer cylinder"
See page 58
■
"Solar"
See page 59
"DHW"
■
See page 60
■
"Additional heat source"
See page 60
Possible change
7F:0
Apartment building; holiday program
can be adjusted separately
91:1
If a combined heating water buffer
to
cylinder is installed, a minimum tem-
91:95
perature for the top of buffer cylinder
(captured by PTS 1) can be set.
Possible change
14:1
Setting range in %
to
14:100