Dhw; Additional Heat Generator - Viessmann Vitoligno 300-C Installation And Service Instructions For Contractors

Pellet boiler
Table of Contents

Advertisement

Codes
Code 1
(cont.)

DHW

Coding
Coding in the delivered condition
DHW differential
0C:0
The differential temperature of
DHW heating (difference between
system temperature and DHW
temperature) is determined auto-
matically.
DHW return temperature
0D:10
Flow control active. Set return tem-
perature corresponds to DHW tem-
perature plus 10 °C

Additional heat generator

Available if code "Additional boiler: Yes", Hardware
group is selected.
Coding
Coding in the delivered condition
Buffer charging until sensor
D0:1
The additional heat source charg-
es the heating water buffer cylinder
up to the first buffer temperature
sensor.
Buffer charging until temperature
D1:75
The additional heat source charg-
es the heating water buffer cylinder
until the temperature of 75 °C at
the selected sensor (code
"D0:1-5") is reached.
60
Possible change
0C:0
Fixed setting of differential tempera-
to
ture from 1 °C to 20 °C
0C:20
0D:0
Flow control deactivated. Valve is al-
ways fully opened.
0D:1
Flow control active. Set return tem-
to
perature corresponds to DHW tem-
0D:30
perature plus value set in °C.
Possible change
D0:0
The heating water buffer cylinder
temperatures are ignored.
D0:2
The additional heat source charges
the heating water buffer cylinder up
to the second buffer temperature
sensor.
D0:3
The additional heat source charges
the heating water buffer cylinder up
to the third buffer temperature sen-
sor.
D0:4
The additional heat source charges
the heating water buffer cylinder up
to the fourth buffer temperature
sensor.
D0:5
The additional heat source charges
the heating water buffer cylinder up
to the fifth buffer temperature sen-
sor.
D1:50
Adjustable value in °C
to
D1:100