Combustion Chamber Sight Glass; Mounting The Combustion Chamber Sight Glass - Viessmann Vitocrossal 300 Installation Instructions For Contractors

Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Mounting the burner
If the burner plate is not factory-fitted: Drill the burner
fixing holes in the burner flange. Cut out the burner
aperture with an oxy-acetylene torch.
A
C
E
Ø = Ø B -10
Fig. 26
Boiler door
A
Flame tube
B
Thermal insulation mat
C
In the case of different dimensions, adjust the cut-out
in the thermal insulation of the boiler door to the
flame tube diameter.
After mounting the burner, seal the annular gap
between the flame tube and the thermal insulation
block with thermal insulation mat

Combustion chamber sight glass

Mounting the combustion chamber sight glass

The sight glass casing with accessories is supplied
inside the combustion chamber.
30
(cont.)
D
.
C
Max. flame tube aperture:
B
Burner plate
D
Thermal insulation block
E
Note on fitting thermal insulation mat C
The hole in the mat needs to be 10 mm smaller than
the diameter of the flame tube ( 7
10 mm). The blue side of the mat has to face the com-
bustion chamber.
350 mm
7
= 7
-
C
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cr3b

Table of Contents