Codes
Coding level 2
(cont.)
Coding in the delivered condition
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump "OFF" if outside
temperature (OT) is 1 K higher
than the set room temperature
(RT
set
OT
>
Parameter address A5:...
1
2
3
4
5
6
7
to
15
Coding in the delivered condition
A6:36
Extended economy mode disa-
bled
A7:0
Without mixer economy function
(only for heating circuits with mix-
er)
A8:1
Heating circuit with mixer creates a
demand for the internal circulation
pump (only for systems without low
loss header)
A9:7
With pump idle time: heating circuit
pump "OFF" if set value is modi-
fied by changing the operating
mode or changing the set room
temperature
58
)
RT
+ 1 K
set
With heating circuit pump logic function: heating circuit pump "OFF"
OT
RT
+ 5 K
>
set
OT
RT
+ 4 K
>
set
OT
RT
+ 3 K
>
set
OT
RT
+ 2 K
>
set
OT
RT
+ 1 K
>
set
OT
RT
>
set
OT
RT
- 1 K
>
set
OT
RT
- 9 K
>
set
Possible change
Note
"Important": Observe for code "A3"
A5:0
Without heating circuit pump logic
function
A5:1
With heating circuit pump logic func-
to
tion: heating circuit pump "OFF"
A5:15
(see the following table)
Possible change
A6:5
Extended economy mode enabled,
to
i.e. the burner and heating circuit
A6:35
pump are switched off at a variable
value, adjustable from 5 to 35 °C
plus 1 °C. Mixer is being closed. The
basis for this is the adjusted outside
temperature. This is composed of
the actual outside temperature and a
time constant that takes account of
the way an average building cools
down.
A7:1
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
If the mixer has been attempting to
close for longer than 20 min.
Heating circuit pump "ON":
If the mixer changes to control
function
If there is a risk of frost
A8:0
Heating circuit with mixer creates no
demand for internal circulation pump
A9:0
Without pump idle time
A9:1
With pump idle time, adjustable from
to
1 to 15. The higher the value, the
A9:15
longer the pump idle time.