Viessmann Vitoladens 300-W Installation And Service Instructions For Contractors page 50

Wall mounted oil condensing boiler for the combustion of fuel oil to din 51603-1 el (low sulphur)
Table of Contents

Advertisement

Codes
Coding level 2
(cont.)
Coding in the delivered condition
3E:0
At signal "External blocking" the in-
ternal circulation pump stays in
control mode
3F:0
At signal "External demand" the in-
ternal circulation pump stays in
control mode
4b:0
Function of input
Room temperature controller
(Vitotrol 100). Only for constant
temperature control units.
51:0
When there is a heat demand, the
internal circulation pump always
starts
52:0
Without flow temperature sensor
for low loss header
54:0
Without solar thermal system
6E:50
No correction of measured outside
temperature
76:0
Without LON communication mod-
ule
77:1
LON subscriber number
79:1
With LON communication module:
control unit is fault manager.
50
Possible change
3E:1
3E:2
3F:1
3F:2
:
4b:1
lH
4b:2
51:1
51:2
52:1
54:1
54:2
54:4
6E:0
to
6E:100
76:1
77:2
to
77:99
79:0
At signal "External blocking" the in-
ternal circulation pump is stopped
At signal "External blocking" the in-
ternal circulation pump is started
At signal "External demand" the in-
ternal circulation pump is stopped
At signal "External demand" the in-
ternal circulation pump is started
External demand
External blocking
System with low loss header:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
The circulation pump stops on expiry
of the run-on time.
System with heating water buffer
cylinder:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
The circulation pump stops on expiry
of the run-on time.
With flow temperature sensor for low
loss header (automatic recognition)
With Vitosolic 100 (automatic recog-
nition)
With Vitosolic 200 (automatic recog-
nition)
With solar control module SM1 with
auxiliary function, e.g. central heat-
ing backup (automatic recognition)
Outside temperature correction in
0.1 K steps
0 to 49 = -5 K to -0.1 K
51 to 100 = 0.1 K to 5 K
With LON communication module
(automatic recognition)
LON subscriber number adjustable
from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note
Allocate each number only once.
Control unit is not fault manager.