Boiler - Viessmann Vitoladens 300-W Installation And Service Instructions For Contractors

Wall mounted oil condensing boiler for the combustion of fuel oil to din 51603-1 el (low sulphur)
Table of Contents

Advertisement

Codes
Coding level 2
(cont.)
Coding in the delivered condition
99:0
Never adjust
9A:0
Never adjust
9b:70
Set flow temperature for external
demand 70 °C
9C:20
Monitoring LON subscribers.
If there is no response from a sub-
scriber for 20 min, the values
specified in the control unit are
used. Only then will a fault mes-
sage be issued.
9F:8
Differential temperature 8 K; only
in conjunction with a heating circuit
with mixer

Boiler

Coding
Coding in the delivered condition
04:1
Minimum burner pause time sub-
ject to boiler load (specified by
boiler coding card)
06:...
Maximum limit of the boiler water
temperature, specified in °C by
boiler coding card
0d:0
Never adjust.
0E:0
Never adjust.
21:0
No service interval set (in hours
run)
23:0
No time set for burner service in-
terval
24:0
"Service" not shown on the dis-
play
29:0
Burner fuel consumption: no me-
tering
2E:0
Never adjust.
2F:0
Venting program/filling program
disabled
30:1
Internal variable speed circulation
pump (set automatically)
52
Possible change
9b:0
Set flow temperature for external de-
to
mand adjustable from 0 to 127 °C
9b:127
(limited by boiler-specific parame-
ters)
9C:0
No monitoring
9C:5
Time adjustable from 5 to 60 min
to
9C:60
9F:0
Differential temperature adjustable
to
from 0 to 40 K
9F:40
Possible change
04:0
Minimum burner pause time set per-
manently (specified by boiler coding
card)
06:20
Maximum limit of boiler water tem-
to
perature within the ranges specified
06:127
by the boiler
21:1
The number of hours run before the
to
burner should be serviced is adjust-
21:100
able from 100 to 10,000 h
One adjusting step
23:1
Time interval adjustable from 1 to
to
24 months
23:24
24:1
"Service" is shown on the display
(address is automatically set and
must be manually reset after a serv-
ice has been carried out)
29:1
Entry of 0.1 to 25.5; 1 step
to
gallon/h
29:255
2F:1
Venting program enabled
2F:2
Filling program enabled
30:0
Internal circulation pump not speed-
controlled (e.g. temporarily for serv-
ice)
100 h
0.1 l or