Boiler; Dhw - Viessmann Vitoladens 300-W Installation And Service Instructions For Contractors

Wall mounted oil condensing boiler for the combustion of fuel oil to din 51603-1 el (low sulphur)
Table of Contents

Advertisement

Codes
Coding level 1
(cont.)
Coding in the delivered condition
Supply temperature setpoint with external demand
9b:70
Set flow temperature for external
demand 70 °C

Boiler

Coding
Coding in the delivered condition
Burner service in 100 hours
21:0
No service interval set (in hours
run)
Service interval in months
23:0
No time set for burner service in-
terval
Service status
24:0
"Service" not shown on the dis-
play
Filling/venting
2F:0
Venting program/filling program
disabled

DHW

Coding
Coding in the delivered condition
DHW temperature setpoint reheating suppression
67:40
For solar DHW heating: set DHW
temperature 40 °C. Above the se-
lected set temperature reheating is
suppressed.
Enable DHW re-circ pump
73:0
DHW circulation pump: "ON" ac-
cording to time program
42
Possible change
9b:0
Set flow temperature for external de-
to
mand adjustable from 0 to 127 °C
9b:127
(limited by boiler-specific parame-
ters)
Possible change
21:1
The number of hours run before the
to
burner should be serviced is adjust-
21:100
able from 100 to 10,000 h
One adjusting step
23:1
Time interval adjustable from 1 to
to
24 months
23:24
24:1
"Service" is shown on the display
(address is automatically set and
must be manually reset after a serv-
ice has been carried out)
2F:1
Venting program enabled
2F:2
Filling program enabled
Possible change
67:0
Set DHW temperature adjustable
to
from 0 to 95 °C (limited by boiler-
67:95
specific parameters)
73:1
"ON" from once per hour for 5 min
to
up to 6 times per hour for 5 min dur-
73:6
ing the time program
73:7
Constantly "ON"
100 h