BA648CF-F
FOUNDATION™ fieldbus
Panel mounting
8 variable
Fieldbus Indicator
Issue 3
Issue: 3
rd
23
June 2011

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BA648CF-F and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for BEKA BA648CF-F

  • Page 1 BA648CF-F FOUNDATION™ fieldbus Panel mounting 8 variable Fieldbus Indicator Issue 3 Issue: 3 June 2011...
  • Page 2: Table Of Contents

    5.3.10 Configuration of bargraph 5.3.11 Scale numeric display 5.3.12 Access code for listener configuration menu. 5.3.13 Change from listener to node 5.3.14 Reset the indicator to listener factory defaults. The BA648CF-F is CE marked to show compliance with the European EMC Directive 2004/108/EC...
  • Page 3: Description

    Fig 1 Typical FOUNDATION™ Fieldbus segment When configured as a fieldbus listener the BA648CF-F is not visible to the fieldbus host and can only be configured using the push buttons on the front of the instrument. Housed in a robust 72 x 144 panel mounting DIN...
  • Page 4: Installation

    4. INSTALLATION 4.2 Installation Procedure 4.1 Location a. Insert the BA648CF-F into the instrument The BA648CF-F is housed in a robust aluminium panel cut-out from the front of the panel. enclosure with a toughened glass window mounted in a Noryl bezel.
  • Page 5: Configuration

    FOUNDATION™ fieldbus Interface Guide which Last variable may be downloaded from www.beka.co.uk For each of the eight inputs: As a fieldbus listener the BA648CF-F is not visible Decimal point XXX.XX to the fieldbus host and can only be configured via...
  • Page 6: Node Configuration Menu

    ‘SCAn’ is the simplest method of configuration if unrestricted access to the configuration menu. the fieldbus Device Address and Variable Identity of the data to be displayed by the BA648CF-F To enter a new access code select ‘CodE’ in the listener are not known.
  • Page 7: Access

    Each of the eight listener inputs in-1 obtained by operating the P and E buttons to in-8 may be enabled or disabled simultaneously. If the BA648CF-F is not protected without affecting any parameters. by an access code the first parameter 'SCAn’ will See section 5.3.6...
  • Page 9 P which will reveal the hexadecimal If one of the eight BA648CF-F indicator’s inputs in- Device Address and Variable Identity of the first 1 to in-8 has not had a Device Address and publisher found as shown in Fig 5.
  • Page 10: Scale Numeric Display

    5.3.7 Enter Device Address ‘Adr’ The ▼ or ▲ button will scroll through the four This function allows a known fieldbus Device options, when required justification Address to be entered and allocated to the displayed, pressing E will enter the selection and indicator input selected in the Edit function.
  • Page 11: Access Code For Listener Configuration Menu

    ‘rESEt’ Again the flashing digit may be changed by The BA648CF-F indicator may be reset to the operating the ▼ or ▲ button and the P button will listener factory defaults shown below: move control to the next digit or to the decimal point.
  • Page 12: Maintenance

    ENSURE PLANT SAFETY BEFORE If a BA648CF-F indicator fails to function during STARTING MAINTENANCE commissioning the following procedure should be followed: If a BA648CF-F fails after it has been functioning correctly, the table shown in section 6.1 may help Symptom Cause Check: to identify the cause of the failure.
  • Page 13: Accessories

    7.2 Tag number The BA648CF-F can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals.