3 - HANDLING
3
Disconnect the electrical connectors on the control and disconnect switch.
4  You can now separate the blocks.
Note: Follow the procedure in reverse to re-couple the blocks, particularly for the 39HXEZ100 & 150.
When uncoupling the blocks, ensure that the 18X10 PVC gasket located between the blocks remains correctly in place 
to guarantee a perfect seal. If necessary, fit one.
NB: if there is a roof, remove it first in accordance with the instructions given on the roof fitting plan (see technical specifications).
39HXC, 39HXE, 39HXEZ and 39HXV models
These models are placed directly on a flat, smooth floor. The flatness value must be the best possible, around one per thousand. 
Under normal conditions of use, there is no need to fix the unit to the floor.
The  unit's  support  feet  must  be  standing  fully  on  their  contact  surface.  It is  important  to  allow  sufficient  service  space  to  facilitate 
maintenance operations.