NZ2MF2S1-32DT DC input/transistor output module
Item
Station type
Number of input points
Rated input voltage
Rated input current
Isolation method
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input response time
Input type
Number of output points
Rated load voltage
Max. load current
Isolation method
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
Output response time
Surge suppressor
External power supply for
output part
Output type
Protection function
Wiring method for common
Withstand voltage
Insulation resistance
*2
Noise immunity
Protection degree
External interface
Applicable DIN rail
Applicable wire size
Applicable solderless
terminal
Number of occupied stations
Reference response time
3 SPECIFICATIONS
50
3.2 Performance Specifications
NZ2MF2S1-32DT
Input specifications
Slave station
16 points
24VDC (ripple rate: 5% or less) (Allowable
voltage range: 20.4 to 28.8VDC)
6.0mA TYP. (for 24VDC)
Photocoupler isolation
100%
15VDC or more/4mA or more
5VDC or less/1.7mA or less
3.8k
*1
OFFON
0ms
(Initial setting: 10ms)
ONOFF
Positive common type
OFFON
ONOFF
Voltage
Current
Overload protection
function
Overheat protection
function
16 points/common (1-wire, spring clamp terminal
block type)
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (Two-piece spring clamp terminal block)
I/O part
34-point two-piece spring clamp terminal block
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715/JIS C 2812)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
For power supply
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
For I/O
Terminal block for module
Page 81 Applicable solderless terminal
*3
power supply and FG
*3
Page 85 Applicable solderless terminal
I/O terminal block
One station
1ms
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
Output specifications
16 points
24VDC (ripple rate: 5% or less) (Allowable
voltage range: 20.4 to 28.8VDC)
0.5A/point, 4A/common
Photocoupler isolation
Current is limited by the overload protection
function.
0.1mA or less
0.3VDC(TYP.)0.5A, 0.6VDC(MAX.)0.5A
0.5ms or less
1.5ms or less (resistance load)
Zener diode
24VDC (ripple rate: 5% or less) (Allowable
voltage range: 20.4 to 28.8VDC)
15mA or less (TYP. 24VDC per common)
External load current is not included.
Sink type
Limited current when detecting overcurrent: 1A or
more/point
Activated to each point.
Activated to each point.
16 points/common (1-wire, spring clamp terminal
block type)
*4
*4