NZ2MF2S2-16R contact output module
Item
Station type
Number of output points
Rated switching voltage/current
Minimum switching load
Maximum switching load
Output response time
OFFON
ONOFF
Life
Mechanical
Electrical
Maximum switching frequency
Surge suppressor
Fuse
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
External interface
Communication part
Module power supply part
I/O part
Applicable DIN rail
Applicable wire size
For power supply
For I/O
Applicable solderless
Terminal block for module
terminal
power supply and FG
Terminal block for
*1
output
Number of occupied stations
Reference response time
Communication cable
Module power supply
Voltage
Current
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG or the terminal block for output.
Multiple wires cannot be connected to a terminal. Connecting two or more wires may cause a poor contact.
*2 It is recommended to use the bar solderless terminal for wiring.
NZ2MF2S2-16R
Slave station
16 points
24VDC 2A (resistance load)/point, 8A/common
240VAC 2A (COS = 1)/point, 8A/common
5VDC 1mA
264VAC 125VDC
10ms or less
12ms or less
20 million times or more
Rated switching voltage/current load 100 thousand times or more
Page 69 Relay life (contact switching life)
3600 times/hour
None
None
2300VACrms for 1 minute between all AC external terminals and the ground
510VACrms for 1 minute between all DC external terminals and the ground
10M or higher between all AC external terminals and the ground, all DC external terminals and the
ground (500VDC insulation resistance tester)
Noise voltage: 1500Vp-p (AC type), 500Vp-p (DC type), noise width 1s, noise frequency 25 to 60Hz
(noise simulator condition)
IP1X
16 points/common (2-wire, terminal block type)
RJ45 connector
Terminal block for module power supply and FG (Two-piece spring clamp terminal block)
34-point two-piece spring clamp terminal block
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715/JIS C 2812)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
Page 81 Applicable solderless terminal
*1
Page 85 Applicable solderless terminal
One station
1ms
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
153mA or less (24VDC, all points ON)
0.30kg
*2
*2
3 SPECIFICATIONS
3.2 Performance Specifications
3
31