Mitsubishi Electric NZ2MF2S2-16A User Manual page 135

Cc-link ie field network basic remote i/o module
Table of Contents

Advertisement

EMC Directive related standards
■Emission requirements
Standard
Test item
EN61131-2: 2007
CISPR16-2-3
Radiated emission
CISPR16-2-1,
CISPR16-1-2
Conducted emission
*1 QP: Quasi-peak value, Mean: Average value
*2 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
■Immunity requirements
Standard
Test item
EN61131-2: 2007
EN61000-4-2
Electrostatic discharge
immunity
EN61000-4-3
Radiated, radio-
frequency,
electromagnetic field
immunity
EN61000-4-4
First transient burst
immunity
EN61000-4-5
Surge immunity
EN61000-4-6
Conducted RF
immunity
EN61000-4-8
Power-frequency
magnetic field immunity
EN61000-4-11
Voltage dips and
interruption immunity
*1 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
*2 The accuracy of an analog-digital converter module may temporarily vary within 10%.
Test details
Radio waves from the product are
*2
measured.
Noise from the product to the power
line is measured.
*2
Test details
Immunity test in which electrostatic
is applied to the cabinet of the
*1
equipment.
Immunity test in which electric
fields are radiated to the product.
*1
Immunity test in which burst noise
is applied to the power line and
*1
signal line.
Immunity test in which lightning
*1
surge is applied to the power line
and signal line.
Immunity test in which high
frequency noise is applied to the
*1
power line and signal line
Immunity test in which the product
is installed in inductive magnetic
*1
field
Immunity test in which power
supply voltage is momentarily
*1
interrupted
Standard value
• 30M-230MHz QP: 40dBV/m (10m in measurement range)
• 230M-1000MHz QP: 47dBV/m (10m in measurement range)
• 150k-500kHz QP: 79dB, Mean: 66dB
• 500k-30MHz QP: 73dB, Mean: 60dB
Standard value
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M to 1000MHz: 10V/m
• 1.4G to 2.0GHz: 3V/m
• 2.0G to 2.7GHz: 1V/m
• AC/DC main power, I/O power, AC I/O (unshielded): 2kV
• DC I/O, analog, communication lines: 1kV
• AC power line, AC I/O power, AC I/O (unshielded): 2kV CM,
1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
• DC I/O, AC I/O (shielded), analog
CM
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
50Hz/60Hz, 30A/m
• 0%, 0.5 periods, starting at zero-crossing
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
Appendix 6 EMC and Low Voltage Directives
*1
*1
*2
, communication lines: 1kV
APPX
133
A

Hide quick links:

Advertisement

Table of Contents
loading