Checking Gas Connections For Tightness; Checking The Gaskets On The Flue Gas Side; Performing Final Checks - Viessmann Vitocrossal 200 Service Instructions For Contractors

Gas condensing boiler with matrix radiant burner permissible operating pressure 6 bar (0.6 mpa)
Hide thumbs Also See for Vitocrossal 200:
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Checking gas connections for tightness

Danger
Escaping gas leads to a risk of explosion.
Always carry out the following steps:
!
Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into contact
with electrical contacts.
1. Insert new gaskets in all gas fittings that have been
opened and retighten them.

Checking the gaskets on the flue gas side

10 Nm
A
B
Fig. 28
1. Check flue gas collector seals
Note
Check seals at full load operation, for example
using an inspection mirror, gas sensor or thermal
image camera. If required, remove the thermal
insulation components. Traces of condensate on
the outside of flue gas collector
leak.

Performing final checks

1. Carry out final checks in accordance with the
points on pages 16 to 20.
30
2. Open the gas shut-off valve.
3. Check the inlet joints of the gas train for tightness.
4. Start the burner (see page 9).
5. Check for tightness:
C
3
for tightness.
2. Check lip seal
A
3. If required, retighten the flue gas collector at ten-
also indicate a
A
2. Record actual values in the report (on page 72).
Outlet joints of the gas train
Joint between the fan and the boiler door
Joint between the fan and the Venturi pipe
of the boiler flue connection for
B
tightness.
sioning toggles
C
; tighten screws diagonally with
10 Nm. Replace lip seal
B
if it leaks.