Act-Pak® Electronic Instrumentation
Act-Pak® Remote Monitoring is an automatic control translator package. The Model 1100D
is a standard NEMA1 free standing or panel mountable enclosure. The Model 1100DN is
a NEMA4X wall mountable fiberglass enclosure. Each Act-Pak device accepts pulses or
contact closures from metering devices and provides a variety of outputs.
Front Panel Display and Buttons
The display is an eight digit transmissive red LCD,
0.46" high. A green LCD is also available. For
outdoor or high ambient light conditions, reflective
readouts will be supplied.
SELECT: Toggles display and advances menu


selection in the programming mode.
RESET: Resets counter to zero if enabled and


changes display in programming mode.
COUNT DISPLAY: 8-digit, display flashes "tot" over


for an overflow condition.
RATE DISPLAY: 6-digit with an enunciator "R" on the


left side.
Physical Size/Weight
Model
1100D
Length
8-3/4" (22 cm)
Height
3-1/8" (8 cm)
Width
8-9/16" (23 cm)
Weight
4 lbs. (1.8 kg)
Memory
Non-volatile E2PROM memory retains all
programming parameters and the count value when
power is removed.
Models 1100D and 1100DN Quick Guide
1100DN
8-1/2" (21.6 cm)
4-1/4" (11 cm)
6-1/2" (16.5 cm)
4 lbs. (1.8 kg)
Electrical Connections
1. Complete all connections to the metering device
and instrument before applying power.
2. If it becomes necessary to disconnect any of these
connections, first remove the AC power to the
instrument.
Meter or Signal Output
Terminal
Function
Wire Color
Number
Switch Inputs
(Belden 8760)
13
+12VDC
No Connection
16
Input Signal
White
14
Ground
Black
15
Shield
Bare (Shield)
Typical Series 1100 Act-Pak Wiring Connection Diagram
QUI CK G UI DE
Wire Color Solid
State Inputs
(Belden 8770)
Red
White
Black
Bare (Shield)
WQG-10029-01

Advertisement

loading

Summary of Contents for Xylem SENSUS Act-Pak 1100D

  • Page 1 QUI CK G UI DE Act-Pak® Electronic Instrumentation Models 1100D and 1100DN Quick Guide Act-Pak® Remote Monitoring is an automatic control translator package. The Model 1100D is a standard NEMA1 free standing or panel mountable enclosure. The Model 1100DN is a NEMA4X wall mountable fiberglass enclosure.
  • Page 2: Output Requirements

    Act-Pak® Electronic Instrumentation Models 1100D and 1100DN Quick Guide Typical Series 1100 Act-Pak Wiring Connection Diagrams Propeller Meters with E-ROFI Water Meters with High Speed Pickup or Hall Effect Transmitter Gas Meters with Slot Sensors Output Requirements Proportional Output Option L Proportional Output: 4-20 mA, 500 ohms maximum Terminal Number...
  • Page 3: Field Adjustments

    Act-Pak® Electronic Instrumentation Models 1100D and 1100DN Quick Guide To exit the programming mode and save all Field Adjustments parameters step through the module until one of the The Flow Rate Indicator/Totalizer readout modules four main modules is displayed, then press the RST are programmed at the factory and will retain the button until Pro nO displays.
  • Page 4 Act-Pak® Electronic Instrumentation Models 1100D and 1100DN Quick Guide programmed flow rate. This number should and open below the setpoint. To latch or hold the be enhanced as follows. For a W2000 DRE the contacts closed once the flow rate is exceeded set maximum flow rate is 2500 GPM at 20.87 hertz.
  • Page 5 Act-Pak® Electronic Instrumentation Models 1100D and 1100DN Quick Guide Note: If meter output data is available in pulses per cubic foot, this Adjusting Option M Multiplier step can be eliminated. The multiplier circuit is configured in binary coded Multiply the pulses per cubic feet by the quantity decimal (BCD) and is adjustable to any number to be indicated.
  • Page 6: Test Equipment Setup

    Act-Pak® Electronic Instrumentation Models 1100D and 1100DN Quick Guide Calibration: Proportional Output (4-20 mA) with a Calibrating D/A Converter Voltmeter The D/A converter is factory set to the specified 1. Connect a load resistor across terminals #5 (+) and frequency (noted on the label affixed to main #6 (-).
  • Page 7 Act-Pak® Electronic Instrumentation Models 1100D and 1100DN Quick Guide Connection Instructions for Models 1100D and CAUTION 1104 Version E Instruments DO NOT connect the 4-20 mA output into a powered loop. 1. Remove the four (4) screws securing the terminal cover plate to the enclosure.

This manual is also suitable for:

Sensus act-pak 1100dn