Operation; Initial Power Up; Standby - KIRLOSKAR DV Series O & M Manual

Table of Contents

Advertisement

Outputs
o
Fuel control options ETR (Energise to run) or ETS (energise to stop).
o
Fuel Pull in output for 2 stage solenoid control.
o
Preheat output for engines in cold climates.
o
Contactor A output for removing the load from the mains.
o
Contactor B output for transferring the load to the generator.
o
General Alarm output indicating abnormal operation.
o
Seven totally isolated dry contact configurable outputs.
o
Excitation.
Inputs (can be either N.C. or N.O.)
o
Trip input for optionally delayed external trip.
o
Emergency Stop input to immediately stop the engine or prevent it from starting
o
Separate analog and digital Oil Pressure inputs for analog sensors, and/or digital switches with
selectable protection options.
o
Fuel level (both resistive and switch)
o
Engine temperature (both resistive and switch)
o
Coolant level low and very low
o
V Belt broken
o
Canopy Temperature options for KG08 temperature sensor or switch input
o
Auto Start input
o
User analog Input
Mechanical
o
Front fixed by vibration proof rivets.
o
Standard 91 x 91 mm Din Standard cut-out.
o
Standard Molex Minifit connectors for low cost, simple tooling and reliability
o
IP65 from the front

4.14.3 Operation

Initial Power Up

On initial power up, the unit displays "Kirloskar Green Power Ideas" as a company logo. Then it displays
Serial number, Application code and Software version.
If configured to maintain its mode during power down, it powers up in the same mode as last powered
down. Otherwise it powers up in manual mode.
If this is the very first power up the mode will default to manual mode.

Standby

When the unit is in standby all measuring systems and display systems are turned off. However the unit
wakes from time to time to check for any unusual conditions and if it finds none it goes back to sleep,
otherwise it alarms accordingly.
Any activity on the Autostart or Emergency Stop inputs or front panel buttons immediately wakes the unit
and the appropriate action is taken.
When "Ready" is shown on the LCD display, the unit is awake and if no action occurs for 1 minute the unit
will go to sleep.
49