Alpha Tri Power X33 TE Installation And Operation Manual

Alpha Tri Power X33 TE Installation And Operation Manual

10-60 kva ups

Advertisement

Tri Power X33 TE
10-60 kVA UPS
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Alpha Tri Power X33 TE

  • Page 1 Tri Power X33 TE 10-60 kVA UPS Installation and Operation Manual...
  • Page 2: Table Of Contents

    Tri Power X33 TE 10/20/30/40/60 kVA CONTENTS Preface ........................1 Safety......................... 2 1. Function Description ................... 3 1-1. UPS Block Diagram ..................3 1-2. UPS Outlook View ..................4 2. Installation and Wiring ..................15 2-1. Storage and Installation Environment ............15 2-2.
  • Page 3 Tri Power X33 TE 10/20/30/40/60 kVA 5. Options ........................ 50 5-1. Dry Contact Card ..................50 5-2. RS-485 MODBUS Card ................50 5-3. SNMP Card ....................50 5-4. Temperature Sensor ..................50 5-5. DC Cold Start Kit..................51 5-6. Parallel Communication Cable ..............51 6.
  • Page 4: Preface

    Tri Power X33 TE 10/20/30/40/60 kVA Preface We thank you for the trust in selecting our UPS. Our equipment complies with the European Community directives for professional equipment and is authorize to use the CE marking. The purpose of this manual is to introduce the operating principles of the UPS and to provide instructions for its safe operation.
  • Page 5: Safety

    Tri Power X33 TE 10/20/30/40/60 kVA Safety  Important Rules (1) Please follow these UPS operating instructions to ensure safe and proper operation. (2) When the UPS is being moved or operated, please ensure that the machine is standing vertically. Do not shake or tip over the machine. Avoid heavy impact.
  • Page 6: Function Description

    Tri Power X33 TE 10/20/30/40/60 kVA Function Description 1-1 UPS Block Diagram This UPS provides Mains input and Bypass input for dual inputs application. The system block diagram as shown below. Bypass Input Mains Input Load Battery Input Input Switch...
  • Page 7: Ups Outlook View

    Tri Power X33 TE 10/20/30/40/60 kVA 1-2 UPS Outlook View  10-40kVA Front View 440mm Control Panel with Colorful LCD Touch Screen Ventilation Grille Handle with Lock Wheels for Handling...
  • Page 8 Tri Power X33 TE 10/20/30/40/60 kVA  10-20kVA Right Side View Through Hole for Parallel Communication Cable...
  • Page 9 Tri Power X33 TE 10/20/30/40/60 kVA  10-20kVA Internal View Parallel Communication Ports HMI Communication Port Communication Selector for Service only USB Port for Service Only Terminal Resistor Setting Switch for Parallel Communication Status LED Indictors Backfeed Protection Communication Card Slot2...
  • Page 10 Tri Power X33 TE 10/20/30/40/60 kVA  10-20kVA Rear View 10kVA 20kVA X50: Output Connections Terminal X10/ X40: Mains/ Bypass Input (3N, 3L3, 3L2, 3L1) Connections Terminal X20: External Battery Connections (1N, 2N, 1L3, 2L3, 1L2, 2L2, 1L1, 2L1) Terminal (B+, N, B-)
  • Page 11 Tri Power X33 TE 10/20/30/40/60 kVA  30-40kVA Right Side View Through Hole for Parallel Communication Cable...
  • Page 12 Tri Power X33 TE 10/20/30/40/60 kVA  30-40kVA Interval View Parallel Communication Ports HMI Communication Port Communication Selector for Service Only USB Port for Service Only Terminal Resistor Setting Switch for Parallel Communication Status LED Indictors Backfeed Protection Communication Card Slot2...
  • Page 13 Tri Power X33 TE 10/20/30/40/60 kVA  30-40kVA Rear View 30kVA 40kVA X50: Output Connections Terminal X10/ X40: Mains/ Bypass Input Connections (3N, 3L3, 3L2, 3L1) Terminal X20: External Battery Connections (1N, 2N, 1L3, 2L3, 1L2, 2L2, 1L1, 2L1) Terminal (B+, N, B-)
  • Page 14 Tri Power X33 TE 10/20/30/40/60 kVA  60kVA Front View Stationary Type Wheel Type (Without Wheel) Control Panel with Colorful LCD Touch Screen Ventilation Grille Handle with Lock Wheels for Handling...
  • Page 15 Tri Power X33 TE 10/20/30/40/60 kVA  60kVA Left Side View Stationary Type Wheel Type (Without Wheel) Through Hole for Parallel Communication Cable...
  • Page 16 Tri Power X33 TE 10/20/30/40/60 kVA  60kVA Internal View ○ Parallel Communication Ports HMI Communication Port Communication Selector for Service Only USB Port for Service Only Terminal Resistor Setting Switch for Parallel Communication Status LED Indictors Backfeed Protection Communication Card Slot2 Communication Card Slot1 ○...
  • Page 17 Tri Power X33 TE 10/20/30/40/60 kVA  Rear Side of Front Door View ○ ○ USB Port for Setting Software Output & Input Contacts SD Card Slot RS-232 Port for Setting Software Communication Port for Remote External Battery Temperature Connector Panel Please find the detail descriptions of above items on section 2-5.
  • Page 18: Installation And Wiring

    Tri Power X33 TE 10/20/30/40/60 kVA Installation and Wiring Storage and Installation Environment  Storage Environment  Temperature -20℃~70℃  Relative Humidity ≦95%  Installation Environment A proper installation environment not only ensures the effective operation of the UPS but also reduces the chance of failure and extends service life. Please take the following recommendations into account to select the most suitable environment and reduce the likelihood of accidents.
  • Page 19: Unpacking, Removing And Fixing Ups

    Tri Power X33 TE 10/20/30/40/60 kVA 2-2 Unpacking, Removing and Fixing UPS This section describes the unpacking and removing processes for wheel type.  Remove the packing materials and cut straps. Remove the cardboard box. 10-40kVA 60kVA  Unscrew the fastening rail kits on the front and rear side of 10-40kVA, and right and left side of 60kVA.
  • Page 20 Tri Power X33 TE 10/20/30/40/60 kVA  Put 2 fastening rail kits on the pallet edge and make them steady by fastening 4 screws in the pallet. 10-40kVA 60kVA...
  • Page 21 Tri Power X33 TE 10/20/30/40/60 kVA  Raise 2 wheel-brakes or expansion foots for remove the UPS from the pallet. Wheel-Brake 10-40kVA Wheel-Brake 60kVA...
  • Page 22 Tri Power X33 TE 10/20/30/40/60 kVA  Block 2 wheel-brakes or adjust the expansion foots to fix the UPS. Wheel-Brake 10-40kVA Wheel-Brake 60kVA...
  • Page 23 Tri Power X33 TE 10/20/30/40/60 kVA  Floor Fixing for 10-40kVA It is possible to reuse the fastening rail kits to fix the UPS to the floor.
  • Page 24 Tri Power X33 TE 10/20/30/40/60 kVA  Floor Fixing for 60kVA Stationary Type(Without Wheel)
  • Page 25 Tri Power X33 TE 10/20/30/40/60 kVA  Floor Fixing for 60kVA Wheel Type It is possible to reuse the fastening rail kits to fix the UPS to the floor.
  • Page 26: General Requirement For Ventilation And Maintenance

    Tri Power X33 TE 10/20/30/40/60 kVA 2-3 General Requirement for Ventilation and Maintenance During installation ensure that the following conditions are met.  Keep at least 1000 mm of free space in front of the UPS for air flow and future maintenance purposes.
  • Page 27: Power Cables Connections

    Tri Power X33 TE 10/20/30/40/60 kVA 2-4 Power Cables Connections  Power Cable Sizing The drawing below shows the positions of power terminals. Mains(X10)/ Bypass(X40) Output Battery 10kVA Power Terminal Positions Mains(X10)/ Bypass(X40) Output Battery 20kVA Power Terminal Positions...
  • Page 28 Tri Power X33 TE 10/20/30/40/60 kVA Mains(X10)/ Bypass(X40) Output Battery 30kVA Power Terminal Positions Mains(X10)/ Bypass(X40) Output Battery 40kVA Power Terminal Positions...
  • Page 29 Tri Power X33 TE 10/20/30/40/60 kVA Battery Mains/ Bypass Output 60kVA Power Terminal Positions  Maximum Current Maximum Max. Max. Battery Input/ Output Output Power Input Output/ Bypass Discharge Voltage Current Input Current Current 10kVA/10KW 19 A 15 A 35 A...
  • Page 30 Tri Power X33 TE 10/20/30/40/60 kVA  Recommended Size of Cables Mains Input Output/ Bypass Input External Battery Capacity R/S/T/N R/S/T/N +/-/N 10kVA 5 mm 3 mm 5 mm 3 mm 8 mm 3 mm 20kVA 8 mm 5 mm...
  • Page 31 Tri Power X33 TE 10/20/30/40/60 kVA  Electrical System Connections  UPS with single Input 3P+N Load  UPS with single input and isolation transformer 3P+N Load  UPS with dual inputs 3P+N 3P+N Load...
  • Page 32 Tri Power X33 TE 10/20/30/40/60 kVA  UPS with dual inputs and isolation transformer 3P+N 3P+N Load 3P+N 3P+N Load 3P+N 3P+N Load Note : You have to install an isolation transformer on one of the inputs if the two...
  • Page 33 Tri Power X33 TE 10/20/30/40/60 kVA  UPS in parallel, use separate battery 3P+N Load  UPS in parallel, use common battery 3P+N Load...
  • Page 34 Tri Power X33 TE 10/20/30/40/60 kVA  UPS in parallel with output transformer Please do not use separate output transformer for each UPS. A common output transformer is recommended. 3P+N Load 3P+N Load...
  • Page 35 Tri Power X33 TE 10/20/30/40/60 kVA  Converter Mode Please do not connect the bypass input. 3P+N Load 3P+N Load Note : Up to 6 units can be operated in parallel for Converter Mode operation and common battery function is available.
  • Page 36: Communication Cables Connections

    Tri Power X33 TE 10/20/30/40/60 kVA 2-5 Communication Cables Connections 10-40kVA 60kVA  Paral-1& Paral-2 — parallel communication port Parallel communication cables are required to connect UPS each other when UPSs operation in parallel. Please refer to section 2-6 for detail connections.
  • Page 37 Tri Power X33 TE 10/20/30/40/60 kVA  LED Status Indictors Normal : The UPS is normal. Alarm : The UPS has some abnormal conditions.  EPO-- Emergence Power Off This EPO contact allows you to turn off the UPS in an emergency. Short these contact to turn off the UPS immediately.
  • Page 38 Tri Power X33 TE 10/20/30/40/60 kVA  USB Complies with USB V.2.0, 12 Mbps Pin Assignment: 1  VCC (+5V) 2  D- 3  D+ 4  Ground This port is available for change the setting of UPS by setting software.
  • Page 39 Tri Power X33 TE 10/20/30/40/60 kVA  Output & Input Contacts The UPS provides 3 output dry contacts and1 input contact. Specification of Output dry contact:250 VAC/ 2 A; 30 VDC/2 A There have 3 jumpers (J1~J3) to set NC/NO for each output contact.
  • Page 40: Ups Parallel Connections

    Tri Power X33 TE 10/20/30/40/60 kVA 2-6 UPS Parallel Connections The UPS can be operated in parallel for extend the capacity and enhances system reliability.  Up to 6 UPS units can be operated in parallel.  The size and length of the input and output cables must be identical for all UPS units.
  • Page 41 Tri Power X33 TE 10/20/30/40/60 kVA  When installing the parallel communication cables, please let the parallel communication cable through the hole at side of UPS, as shown below.
  • Page 42 Tri Power X33 TE 10/20/30/40/60 kVA  Recommended 1+1 parallel system configuration Mains Mains Bypass Parallel Communication Cables Load Load 1+1 parallel, Single Input 1+1 parallel, Dual Input...
  • Page 43 Tri Power X33 TE 10/20/30/40/60 kVA  Recommended N+1 parallel for single input system configuration Mains Parallel Up to 6 UPS Units Communication External Cables Manual Bypass Switch Load...
  • Page 44 Tri Power X33 TE 10/20/30/40/60 kVA  Recommended N+1 parallel for dual input system configuration Mains Bypass Parallel Up to 6 UPS Units Communication External Cables Manual Bypass Switch Load...
  • Page 45: Operation Description

    Tri Power X33 TE 10/20/30/40/60 kVA Operation Descriptions 3-1 Operating Mode The UPS provides the following operating modes: (1) Normal Mode (Online Mode): In Normal mode, grid power is passed through Rectifier then used to charge the battery and provide power through the Inverter simultaneously. Different output voltages settings can be set in VFI mode.
  • Page 46: Online Operations

    Tri Power X33 TE 10/20/30/40/60 kVA 3-2 Online Operations An online UPS provides stable power that is not affected by an unstable main power supply (ex. grid power). Through the online UPS, grid power can provide a clean, noise- free power supply environment.
  • Page 47: Operation Processes

    Tri Power X33 TE 10/20/30/40/60 kVA 3-4 Operation Processes 3-4-1 Normal Mode Start-up (1) Close UPS Mains Input and Bypass Input Switches. →Command→Operation→Normal mode on LCD display. The (2) Select UPS will be started and supply output voltage. (3) Close UPS Output Switch to supply the power to the load.
  • Page 48: Control Panel Operation And Function Description

    Tri Power X33 TE 10/20/30/40/60 kVA Control Panel Operation and Function Description Each UPS is equipped with a LCD touch panel to provide the user with a simple and intuitive user interface that is easy to learn. The touch panel offers a combination of graphics and numbers that make it easy to determine the input/output voltage, frequency, load and battery level at a glance.
  • Page 49: Menu

    Tri Power X33 TE 10/20/30/40/60 kVA 4-2 Menu Click to enter to Menu screen as shown in above picture. Slide the screen to switch to other menu page and click the menu icon to enter to the desire function. Click to hide/show the sub-menu.
  • Page 50 Tri Power X33 TE 10/20/30/40/60 kVA All menu functions are showing in below table. Menu Sub-Menu Functions Display the UPS status、alarm、operating mode and Mimic Display measurements. Please refer to section 4-3 for more detail.  Normal mode  ECO mode ...
  • Page 51 Tri Power X33 TE 10/20/30/40/60 kVA Menu Sub-Menu Functions Schedule Display the schedule. Schedule To define the schedule for ECO mode. Management Setting Battery Test To define the schedule for battery test. Schedule Language Select the display language Update Prog.
  • Page 52: Mimic Display

    Tri Power X33 TE 10/20/30/40/60 kVA 4-3 Mimic Display 【A】is Rectifier、【B】is Static Switch and 【C】is Inverter. The fade pattern indicates this part isn’t activated. The blue pattern indicates this part is activated. The red pattern indicates this part is occurred abnormal condition.
  • Page 53: Options

    Tri Power X33 TE 10/20/30/40/60 kVA Options 5-1 Dry Contact Card This card provides six output dry contacts and six input contact. These contacts are programmable and user can change the definition for each contact. Please refer to Dry Contact Card manual for more detail.
  • Page 54: Temperature Sensor

    Tri Power X33 TE 10/20/30/40/60 kVA 5-4 Temperature Sensor 3000.0mm 4.3mm 7.2mm Measure the battery temperature. DC Cold Start Kit This kit allows UPS start-up by the battery without mains input. 5-6 Parallel Communication Cable The parallel communication cables are required when UPS in parallel. Each UPS provides a 1.5 meters parallel communication cable as standard and it can use for 2...
  • Page 55: Troubleshooting

    Tri Power X33 TE 10/20/30/40/60 kVA Troubleshooting In the event of failure, the display area on the control panel will highlight the problem area in red. The “Alarm” symbol will also blink to warn that there is a problem with the UPS. Click to have a alarm list as below picture.
  • Page 56: Technical Specification

    Tri Power X33 TE 10/20/30/40/60 kVA Technical Specification Model X33 TE 10 X33 TE 20 X33 TE 30 X33 TE 40 X33 TE 60 Capacity 10 kVA 20 kVA 30 kVA 40 kVA 60 kVA Input Voltage 400V 3 Phase + N ±20% @100% load...
  • Page 57 Tri Power X33 TE 10/20/30/40/60 kVA Model X33 TE 10 X33 TE 20 X33 TE 30 X33 TE 40 X33 TE 60 HMI & Communication Display and MMI 4.3" Colorful LCD Touch Screen Built-in Communication RS-232, USB, EPO, Dry Contacts...
  • Page 58 Tri Power X33 TE 10/20/30/40/60 kVA...
  • Page 59 Tri Power X33 TE 10/20/30/40/60 kVA CONTACT INFORMATION Alpha Technologies GmbH www.alphatechnologies.com Hansastrasse 8 – 91126 Schwabach – Germany Tel.: +49 (0)9122 79889 – 0 Fax: +49 (0)9122 79889 – 21 sales@alphatechnologies.de 192321262006003...