External Input And External Output - Fujitsu AIRSTAGE AJY072LALBH Installation Manual

Table of Contents

Advertisement

(1) Connecting the power supply cable
Caution when wiring cable
1) Use ring terminals with insulating sleeves as shown in the fi gure to connect to
the terminal block.
2) Securely clamp the ring terminals to the cables using an appropriate tool so that
the cables do not come loose.
3) Use the specifi ed cables, connect them securely, and fasten them so that there is
no stress placed on the terminals.
4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
5) Do not tighten the terminal screws too much, otherwise, the screws may break.
6) See the table for the terminal screw tightening torques.
Strip 10 mm
Screw with
special washer
Cable
Ring terminal
Terminal block
Earth (Ground)
Ring terminal: M8
cable
* Use a ring terminal to connect the electric cables to the power supply terminal
board.
(2) Connecting the transmission cable
Sealing transmission cable
Connect both ends of the sealed wires of the transmission cable to the earth terminal
of the equipment or to the earth screw near the terminal.
Be very careful that the screws are not overly tightened as the wires may snap and
the terminal may be damaged.
Wind with insulation tape to
prevent short circuit
Use one side of the
Connect both ends of sealed
twisted-pair cable
cable to earth.
Be sure to use one side of a twisted-pair cable when using transmission cable with 2
sets of twisted-pair cables.
8 to 10 mm
40 mm or more
En-15
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
Cable clamp
IN
RB
Cable clip
Cable tie
(Accessory)
6. 7.

External input and external output

6. 7. 1.
Terminal position
Input 5
Input 4
CN133
CN135
CN134
(WHITE)
(ORANGE)
(RED)
Outdoor unit PC board
Do not bundle the cable for base heater with other cables.
(Example)
In case of Outdoor unit
(1) Insert the connector to CN134 (Red) and CN135 (Orange) of control PC board.
(2) Fix it to the wire with the attached cable tie.
CN135
(Orange)
CN115
(Black)
Clamp
▪ Do not clamp the base heater cable.
6. 7. 2.
External input terminal
• Setting to low noise mode, outdoor unit operation peak control setting, emergency/
batch stop and electricity meter pulse are possible from the outside.
• Except for wattmeter pulse reception (CN135) among external input terminals, only
the Master unit is effective.
Wiring method and specifi cations
2
* A twisted pair cable (0.33 mm
cable is 150 m.
* Use an external input and output cable with appropriate external dimension, de-
pending on the number of cables to be installed
* For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.
Input 3
Input 2
Input 1
Output 1
CN132
CN131
CN136
(GREEN)
(YELLOW)
(BLACK)
CAUTION
Clamp
CN134
(Red)
Cable tie
(Accessory)
Wire
(22AWG)) should be used. Maximum length of
Output 2