Rotary Switch Setting - Fujitsu AIRSTAGE AJY072LALBH Installation Manual

Table of Contents

Advertisement

Outdoor unit PC board
7. 2. 2.
Settings to be confi gured locally
(1) Outdoor unit address setting
When 2 or 3 outdoor units are installed to 1 refrigerant system, set the address for
each outdoor unit.
Set the address for all outdoor units.
SET3
Outdoor unit address
1
2
OFF
OFF
0
OFF
ON
1
ON
OFF
2
ON
ON
-
(2) Number of slave units setting for outdoor unit
Set the number of slave units connected to 1 refrigerant system.
Set only the master unit.
SET3
Number of connectable
outdoor units
3
4
OFF
OFF
0
OFF
ON
1
ON
OFF
2
ON
ON
-
(3) Number of outdoor units installed
The number of outdoor units installed in 1 refrigerant system must be set.
Set for all outdoor units.
SET5
Number of outdoor units
1
2
OFF
OFF
OFF
ON
ON
OFF
ON
ON
7. 2. 3.
Terminal resistor setting
Be sure to set the terminal resistor according to specifi cations.
Set the terminal resistor for every network segment (NS).
If terminal resistor is set in multiple devices, the overall communication system
may be damaged.
If terminal resistor is not set in a device, abnormal communication may occur.
• Be sure to set 1 terminal resistor in a network segment. You can set the terminal
resistor at the outdoor unit or signal amplifi er.
• When setting the terminal resistor of a signal amplifi er, refer to the installation
manual of the signal amplifi er.
• When setting multiple terminal resistors, take note of the following items.
1 How many network segments are there in a VRF system?
2 Where will you set the terminal resistors in a network segment? (Condition for 1
segment: Total number of outdoor and indoor units and signal amplifi ers is less
than 64, or the total length of the transmission cable is less than 500m)
3 How many outdoor units are connected to 1 refrigerant system?
En-17
7 Segment
LED lamp
LED indicator
Rotary switch
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
REF AD
SW106
SW105
X 10
X 1
MODE
SET 1
SET 2
SET 3
SET 4
SELECT ENTER
/EXIT
SW102
SW101
SW103
SW104
SW107
SW108
SW109
Push button
DIP switch
SET5
Remarks
Master unit (Factory setting)
Slave unit 1
Slave unit 2
Forbidden
Remarks
Master unit only (Factory setting)
1 slave unit connected
2 slave unit connected
Forbidden
Remarks
1
(Factory setting)
2
-
3
-
-
Forbidden
CAUTION
Confi gure the setting (DIP switch SET5) of the terminal resistor of the outdoor units as
shown below from conditions 1 to 3.
SET5
Terminal resistor
4
OFF
ON
Figure: Terminal resistor setting
NS1 (Network segment 1)
(Set terminal resistor at outdoor units)
Terminal resistor: on
Refrigerant system1
Master unit
Terminal resistor: off
Refrigerant system2
Master unit
Refrigerant system3
Master unit
NS2 (Network segment 2)
NS3 (Network segment 3)
Terminal resister: on
About the setting of terminal resistor
Outdoor unit (Master unit)
:on
:off
Signal amplifi er
Install
Do not install
7. 3.

Rotary switch setting

The rotary switch (REF AD) sets the refrigerant circuit address of the outdoor unit.
Confi gure the settings only on the master unit of a refrigerant system.
If multiple refrigerant systems are connected, set the rotary switch (REF AD) as
shown in the table below.
Refrigerant circuit address
0
1
2
3
4
97
98
99
Setting
Setting range
Refrigerant circuit
0–99
address
Rotary Switch (REF AD×1): Factory setting "0"
Rotary Switch (REF AD×10): Factory setting "0"
Remarks
Disable
(Factory setting)
Enable
-
NS4 (Network
segment 4)
Rotary Switch Setting
REF AD
×10
0
0
0
0
0
9
9
9
Type of switch
Setting
example
63
REF AD × 10
REF AD × 1
×1
0
1
2
3
4
7
8
9

Advertisement

Table of Contents
loading

Table of Contents