Influence Of Environmental Parameters; Permissible Ambient Conditions; Site Altitude - Siemens 3AF 01 Operating Instructions Manual

Outdoor vacuum switchgear
Table of Contents

Advertisement

The operating and pulse duration times stated in Table 2
below apply for 3AF 01 vacuum circuit-breakers:
Operating times:
Opening time, 1st shunt release (Y1)
Opening time, 2nd shunt release (Y3)
Opening time, suppl.shunt release (Y2)
Arcing time
Break time, 1st shunt release (Y1)
Break time, 2nd shunt release (Y3)
Break time, suppl.shunt release (Y2)
Close-open time, 1st shunt release (Y1)
Close-open time, 2nd shunt release (Y3)
Close-open time, suppl.shunt release (Y2)
Dead time
Closing time with stored-energy mech.
Synchronizing error between the poles
Spring charging times:
Spring charging time (M1)
Minimum pulse duration:
Shunt release (Y1) .. 3AY1510
Supplementary release
(Y2, Y4,Y6) .. 3AX 110_
Closing solenoid (Y9) .. 3AY1510
Table 2: Operating and pulse duration times
2.3

Influence of environmental parameters

2.3.1

Permissible ambient conditions

The 3AF 01 vacuum circuit-breakers are designed for the
normal operating conditions laid down in the standards.
Permissible ambient temperatures:
Maximum value
Average over a period of 24 hours
Minimum value
Permissible relative atmospheric humidity:
Maximum value, 24 hour mean
Maximum value, 1 month mean
Under these conditions, condensation may occur
occasionally.
1320mm creepage is provided on the porcelain
insulators. These are suitable for very high levels of
pollution at site.
2.3.2
≤ 65 ms
The insulating capacity of air decreases with rising
altitude due to the lower air density. In conformity with
≤ 65 ms
IEC 62271-1, the rated lightning impulse voltage values
given in Fig. 5 are valid up to an installation altitude of
≤ 50 ms
1000m above mean sea level. As from an altitude of
<15 ms
1000m, the insulation level must be corrected as shown
in Fig. 4:
≤ 80 ms
≤ 80 ms
≤ 65 ms
≤ 90 ms
≤ 90 ms
≤ 90 ms
300 ms
≤ 75 ms
Fig. 3:
≤ 2 ms
U ≥ U
U
≤ 15 s
U
o
K
a
40 ms
K
= e
a
20 ms
Calculating the altitude compensation factor K
H = Installation altitude in meters
40 ms
m = 1 for AC voltage, lightning impulse voltage
Example:
For a specified rated withstand voltage of 185kV at an
altitude of 1400m, an insulation level of at least 195kV
under standard reference atmosphere is required:
195kV ≥ 185kV • e
+ 55
C
This means that equipment designed for a rated voltage
o
+ 35
C
o
of 195 kV, is required for this application.
- 25
C
o
95 %
90 %
Installation altitude
Altitude compensation factor K
• K
o
a
Rated withstand voltage V under standard reference
atmosphere
Required rated withstand voltage for the
installation location
Altitude compensation factors
m • (H-1000) / 8150
(between the phases, phase-earth, applied
longitudinally)
1*(1400-1000)/8150
a
:
a
= 185 • 1.05
3