MCx-xxxAx-8.09 (12-24 VDC; 4-20 mA Control) USER MANUAL Contents INSTALLATION Mounting Wiring Power Supply and Current Draw Control Signal and Feedback OPERATION DIP switches Controlling the Actuator Changing the number of turns Torque Settings Speed and Torque Details Signal Loss and Calibration Troubleshooting ACTUATOR DIMENSIONS PART NUMBER BREAKDOWN...
Mounting and supported as shown in the image to the Bracket right. The mounting bracket is not supplied by Hanbay. Cable Entry Exceptionally, the actuator may be suspended on the tubing itself but ONLY if the application is vibration free and the tubing is minimum ¼” dia.
The potential of the external GND after the sensing resistor may not be more than +6 VDC / -2 VDC away from the power GND of the actuator. This feedback signal output is only available in HANBAY MCx-xxxAF model actuators. Page 3 of 13 www.hanbayinc.com | 1 800 315 4461...
User Manual MCx-xxxAx-8.09 OPERATION DIP switches The DIP switches allow you to change the settings on your actuator. To flip a switch, gently use a small flat-head screwdriver. See the table below for DIP switch functionality. In this example DIPs 1, 2, 5 and 12 are on. Function Speed: Choose how quickly the actuator will turn the drive wheel.
User Manual MCx-xxxAx-8.09 Changing the number of turns With the DIP switch settings, you can adjust anything between 1 and 31 turns to represent the full signal range of 4-20 mA. Check in the table below. (1 = “On”, 0 = “Off”) Total Turns For more turns, set DIP 4 to the ON position.
User Manual MCx-xxxAx-8.09 Torque Settings Seating power settings: To accommodate different valves and other applications with (when operating at 24 VDC) different torque requirements, the actuator can be set to apply different torque on the valve stem when in the seating mode. DIP 10 DIP 11 Power...
Page 7
User Manual MCx-xxxAx-8.09 MCM-xxxAx Actuators Speed: Torque: Seating Torque (in-lbs) Time for DIP 1 DIP 2 DIP 10 DIP 11 1 turn (sec) 12VDC 24VDC Operating torque is 100% NOTE: If actuator is MCK-xxxAx, divide torque values by 3. To convert in-lbs to Nm, divide by 9. MCH-xxxAx Actuators Speed: Torque:...
User Manual MCx-xxxAx-8.09 Signal Loss and Calibration 1. For actuators that are not connected to a UPS (Uninterruptible Power Supply), the loss of signal will be simultaneous with power loss. Consequently, the actuator will not be able to move anywhere. In the shutdown process, the actual position is automatically saved to the internal EEPROM.
A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator. Remove power. Re-check the wiring and the power/signal apparatus. Power actuator and re-calibrate. If the problem persists, please call Hanbay for technical support. Page 9 of 13 www.hanbayinc.com | 1 800 315 4461...