Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MC-AS-1.05 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Hanbay MC-AS-1.05 Series

  • Page 1: Table Of Contents

    Set the actuator address Modbus Protocol Speed and Torque Settings Speed and Torque Details Writing to All Other Holding Registers Reading the Input Registers Using Hanbay Function Codes Calibration Troubleshooting ACTUATOR DIMENSIONS PART NUMBER BREAKDOWN LABEL BREAKDOWN Page 1 of 18 www.hanbayinc.com | 1 800 315 4461...
  • Page 2: Installation

    Mounting and supported as shown in the image to the Bracket right. The mounting bracket is not supplied by Hanbay. Cable Entry Exceptionally, the actuator may be suspended on the tubing itself but ONLY if the application is vibration free and the tubing is minimum ¼” dia.
  • Page 3: Power Supply And Draw

    User Manual MCx-xxxAS-1.05 Power Supply and Draw The MCx-xxxAS may be connected to voltages ranging within 12-24 VDC. The current draw will range from minimum 100 mA to maximum 3 A while the actuator is active. When not moving, the actuator draws approx. 50 mA. Control Signal and Feedback Locate the correct connection terminals as shown in the picture on p.2, then connect your communication wires to PIN 3 and PIN 4 (grey and pink wires), as shown below.
  • Page 4: Operation

    User Manual MCx-xxxAS-1.05 OPERATION DIP switches The DIP switches allow you to change the settings on your actuator. To flip a switch, gently use a small flat-head screwdriver. See the table below for DIP switch functionality. In this example DIPs 1, 2, 5 and 12 are on. Function Baud Rate: Choose the rate at which information is transferred.
  • Page 5: Set The Actuator Address

    User Manual MCx-xxxAS-1.05 Set the actuator address With the DIP switch selector, you can set any address between 1 and 63. (1 = “On” 0 = “Off”). To change the address, turn off the actuator, change the setting of DIP switches and power it up again. Actuator Dip3 Dip4...
  • Page 6: Modbus Protocol

    02 (0x02) Read Discrete Inputs 03 (0x03) Read Holding Registers. 04 (0x04) Read Input Registers. 06 (0x06) Write Single Register. Hanbay function codes: (see p.13 for examples) 100 (0x64) Re-zero the actuator. 101 (0x65) Close the valve. 102 (0x66) Open the valve.
  • Page 7: Speed And Torque Settings

    User Manual MCx-xxxAS-1.05 Speed and Torque Settings During normal operation, the actuator will try to reach the speed set by “MaximumSpeed”. If the torque required to reach this speed exceeds the actuator model’s capability, the actuator will automatically slow down. Please refer to the tables in the Speed and Torque Details section for each actuator model’s torque capability.
  • Page 8: Speed And Torque Details

    User Manual MCx-xxxAS-1.05 Speed and Torque Details MCL-xxxAS Actuators Speed: Torque: Seating Torque (in-lbs) Maximum Speed Time for Torque Address Address 0x0000 1 turn (sec) 0x0001 12VDC 24VDC Operating torque is 100% NOTE: If actuator is RCJ-xxxAS, divide torque values by 3. To convert in-lbs to Nm, divide by 9.
  • Page 9: Writing To All Other Holding Registers

    User Manual MCx-xxxAS-1.05 Writing to All Other Holding Registers The “NumberOfTurns” register allows the user to set the number of turns the actuator performs in the full signal range. Register name Address Max Min Default Actuator Function Register Register address code address new value...
  • Page 10 User Manual MCx-xxxAS-1.05 The “OutputRangeLow” register allows the user to set the lower limit of the feedback signal (i.e. the value of the feedback signal when the actuator is in the fully closed position). Register name Address Default Actuator Fct. Register Register address...
  • Page 11: Reading The Input Registers

    User Manual MCx-xxxAS-1.05 Signal Loss The “SignalLostPosition” register can be used (optional) to set the position of the actuator upon signal loss. Signal loss can only occur when controlling the actuator with 4-20 mA (or 1-5 V) input signals, i.e. when “TargetFromRS485Flag”...
  • Page 12 User Manual MCx-xxxAS-1.05 The meaning of the value in the “StatusRegister” is described below. Only Bits 0-4 are associated with a physical meaning. Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bits 5 to 15 Discrete input 1 Discrete input 2 Discrete input 3 Discrete input 4...
  • Page 13: Using Hanbay Function Codes

    User Manual MCx-xxxAS-1.05 Using Hanbay Function Codes Register name Address Max Min Default Actuator Function address code 0x0064 Example: Re-zero actuator number 1 0x01 0x64 0x---- 1 byte 1 byte 2 bytes Register name Address Max Min Default Actuator Function...
  • Page 14: Troubleshooting

    A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator. Remove power. Re-check the wiring and the power/signal apparatus. Power actuator and re-calibrate. If the problem persists, please call Hanbay for technical support. Page 14 of 18 www.hanbayinc.com | 1 800 315 4461...
  • Page 15: Actuator Dimensions

    User Manual MCx-xxxAS-1.05 ACTUATOR DIMENSIONS MCJ, MCL & MCM -xxxAS models MCH-xxxAS models Page 15 of 18 www.hanbayinc.com | 1 800 315 4461 Rev.2021.8 hanbaysales@hanbayinc.com...
  • Page 16 User Manual MCx-xxxAS-1.05 MCF-xxxAS models Page 16 of 18 www.hanbayinc.com | 1 800 315 4461 Rev.2021.8 hanbaysales@hanbayinc.com...
  • Page 17: Part Number Breakdown

    User Manual MCx-xxxAS-1.05 PART NUMBER BREAKDOWN Full Hanbay Part Number: Page 17 of 18 www.hanbayinc.com | 1 800 315 4461 Rev.2021.8 hanbaysales@hanbayinc.com...
  • Page 18: Label Breakdown

    User Manual MCx-xxxAS-1.05 LABEL BREAKDOWN Firmware Version AF-1.05 MM = Multiturn AB-1.05 MML = Multiturn Low Torque AS-1.05 MMUL = Multiturn Extra Low Torque QM = Quarter turn QM97 = Quarter turn 97° DT-2.01 DC-2.01 DT-4.06 (Obsolete since 2019) M-Dx V2.31 Actuator Supply Voltage Circuit Board Version 12-24 VDC @ 3.0 A or...

Table of Contents