Main Menu Buttons -
Installation Settings
Timers & Deadbands
The Deadband is the number of degrees or minutes that the
thermostat waits before it initiates the stages of heating or cooling.
1st Stage Deadband Specifies the minimum temperature
difference between the room temperature and the desired
setpoint before the first stage of heating or cooling is allowed
to turn on. For example, if the heat setpoint is 68˚ and the 1st
Stage deadband is set to 2 degrees, the room temperature
will need to drop to 66 degrees before the heat turns on.
1st Stage Deadband
(1 - 6 deg. F)
2nd Stage Deadband
2nd Stage Deadband
Number of degrees past 1st stage before 2nd stage turns on. (0 - 10 deg. F)
2nd Stage Timer
Number of minutes past 1st stage before 2nd stage turns on. (0 - 60 mins.)
(The 2nd stage deadband must also be met)
2nd Stage Turnoff Point
Deadband or Setpoint.
3rd Stage Deadband
Settings
(Continued)
(2˚)
(2˚)
(2mins )
(Deadband)
The 3rd stage deadband
settings have the same
adjustable steps as 2nd
stage deadband.
57