Commissioning, inspection, maintenance
Further details regarding the individual steps
Yes
Burner in opera-
tion.
The green LED on
the ignition trans-
former is perma-
nently on (a flame
is recognised).
For further details regarding faults, see
page 63.
Adjusting the standard burner settings
Standard burner settings
Note
Check that the service instructions are valid for the relevant burner (see applicability
on the last page and the serial no. on the boiler type plate).
A Flue gas test port
Rated output
Burner stage
Rated output
Oil burner nozzle
Make: Danfoss
14
A
kW
12.9/19.3
Stage 1
kW
12.9
Type
80°H LE V
Gph
(cont.)
Stage 2
19.3
0.40
16.1/23.5
Stage 1
Stage 2
16.1
23.5
80°H LE V
0.50