Viessmann Vitoladens 300-W Service Instructions For Contractors page 44

Wall mounted oil fired condensing boiler for the combustion of low sulphur fuel oil din 51603-el-1 with integral boiler control unit
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
Boiler/burner
52:0
Without flow temperature
sensor for low loss
header
54:0
Without solar control unit 54:1
DHW
56:0
DHW temperature adjust-
able from 10 to 60 °C
58:0
Without auxiliary function
for DHW heating
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
5b:0
DHW cylinder directly
connected to the boiler
60:20
During DHW heating, the
boiler water temperature
is max. 20 K higher than
the set DHW temperature
62:2
Circulation pump with
2 min run-on
44
Possible change
52:1
With flow temperature sen-
sor for low loss header
(automatic setting on rec-
ognition)
With a Vitosolic 100
54:2
With a Vitosolic 200 (auto-
matic adjustment after rec-
ognition)
56:1
DHW temperature adjusta-
ble from 10 to above 60 °C
(max. value subject to cod-
ing card)
Observe the maximum per-
missible DHW temperature
58:10
Input of a second set DHW
to
value; adjustable from 10
58:60
to 60 °C
59:1
Starting point adjustable
to
from 1 to 10 K below the set
59:10
value
5b:1
DHW cylinder connected
downstream of the low loss
header
60:5
The difference between the
to
boiler water temperature
60:25
and the set DHW tempera-
ture is adjustable from 5 to
25 K
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15