Firmware Update; Switch-On Sequence Of Electronics/Hydraulics - Bosch rexroth SYDFED 2X Series Manual

Pressure and flow control system
Table of Contents

Advertisement

36/96
SYDFED-2X, SYDFED-3X, SYHDFED-1X | Product description
Recommended
preconditions
Supported operating
systems
Switching on
Switching off
Bosch Rexroth AG, Edition 11.2021, RE 30017-B
IndraWorks Engineering is designed for a screen setting of 96 dpi (default
setting). The use of other settings may result in the fact that screen elements
are displayed incompletely or incorrectly.
• IBM-compatible PC, i5 Quad Core
• RAM: 4 GB with 64-bit operating systems
• Microsoft Windows 10

5.10.2 Firmware update

Uncontrolled movements of the drive!
Risk of injury! All data in the control are overwritten and a software reset is
executed on the control.
▶ Switch the drive motor off! A software reset corresponds to a power-on
reset of the control and may only be carried out when the system is in a safe
condition.
Current firmware is made available by Rexroth together with the project files.
New firmware can be transmitted to the control under menu item "Service" →
"Firmware Administration".
Current firmware projects can also be downloaded from the Rexroth website in the
section "SYDFED" under "Download":
http://www.boschrexroth.com/sydfe
5.11

SWITCH-ON SEQUENCE OF ELECTRONICS/HYDRAULICS

Due to various monitoring routines implemented in the electronic assemblies, fault
messages may be generated in the case of an unfavorable order of switching on.
These error messages cause uncertainties, although they have no "real" cause of
fault.
In principle, it is valid that all SY(H)DFED control systems that are provided with
internal pilot oil supply automatically swivel to the operationally safe zero stroke
position in the event of a power failure. However, a precondition for zero stroke
is a minimum pressure between 8 and 12 bar, which the pump has to build up as
pilot pressure. This can always be ensured, when no oil can flow away from the
pump output (e.g. actuator line hydraulically blocked).
Observe the special case of suspended loads!
Activation sequence of digital electronics SYDFED
1. Voltage supply of the electronics
2. Set controller enable
3. Switch motor on
4. Suppress warnings until target speed has been reached
5. Open check valve (if provided)
1. Command value provision: αcomm = 5 % and p = 10 bar
2. Close check valve (if provided)
3. Suppress warnings
4. Switch el. motor off
5. Switch voltage supply of electronics off
CAUTION

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth sydfed 3x seriesRexroth sydfed 1x series

Table of Contents